To add a potentiometer for speed control, change Parameter #5 
(Standard Speed Source) to  0-10 VDC (03).

Once the PROGRAM mode is accessed, use the 

 and 

 buttons to 

scroll to the desired parameter number, and press the 

Mode

 button 

to see the parameter setting. Use the 

 and 

 buttons to change 

the parameter setting and press 

Mode

 to store the new setting.

Connections:

Below is a sample wiring diagram for two-wire start/stop control.  The 
drive is ready to use right out of the box, with these simple control 
wiring connections; no parameter adjustments are required.  Speed 
is controlled from the 

 and 

 buttons on the front of the drive. 

CONFIGURING THE SCF DRIVE

Entering Program Mode:

To  access  the  parameters,  press  the 

Mode

  button.  This  will 

activate the password prompt. The display will read “00” and the 
right-hand decimal point will be blinking. Use the 

 and 

 buttons 

to scroll to the password value (the factory default password is 225) 
and press 

MODE

 to enter.

Press 

Mode

Upper right decimal point blinks

Press 

Mode

 to enter password

Display reads “00”

Use 

 and 

 to scroll to the password 

value (factory default password is 225)

SCF PARAMETER MENU

No.

Parameter 

Name

Range of Adjustment

Factory Default

01

Line Voltage

High (01), Low (02)

High (01)

02

Carrier Frequency

4 kHz (01), 6 kHz (02), 

8 kHz (03), 10 kHz (04)

6 kHz (02)

03

Start Method

Normal (01), Start on Power-up 

(02), Start w/DC Brake (03), 

Auto Restart w/DC Brake (04), 

Flying Restart 1 (05), Flying Restart 2 (06), 

Flying Restart 3 (07)

Normal (01)

04

Stop Method

Coast (01), Coast with 

DC Brake (02), Ramp (03), 

Ramp with DC Brake (04)

Coast (01)

05

Speed Source

Keypad (01), Preset #1 (02), 

0-10 VDC (03), 4-20 mA (04)

Keypad (01)

06 

13

TB-14 Output 

TB-15 Output

None (01), Run (02), Fault (03), 

Inverse Fault (04), Fault Lockout (05), 

At Set Speed (06),Above Preset #3 (07), 

Current Limit (08), Auto Speed (09), 

Reverse (10), 

Min Alarm (11), 

Max Alarm (12), Min/Max Alarm (13)

None (01) 

None (01)

8

TB-30 Analog Out

None (01), 0-10 VDC Freq (02), 

2-10 VDC Freq (03), 

0-10 VDC Load (04), 

2-10 VDC Load (05)

None (01)

9

TB-31 Analog Out

None (01), 0-10 VDC Load (02), 

2-10 VDC Load (03), 

Dynamic Braking (04)

None (01)

10

TB-13A Select

None (01), 0-10 VDC (02), 

4-20 mA (03), Preset Speed #1 (04), 

Run Reverse (05), Start Reverse (06), 

External Fault (07), Remote Keypad (08), 

DB Fault (09), Auxiliary Stop (10), 

Accel/Decel #2 (11), 

Keypad Setpoint (12)

None (01)

11

TB-13B Select

None (01), 0-10 VDC (02), 

4-20 mA (03), Preset Speed #2 (04), 

Decrease Freq (05), Jog Forward (06), 

Jog Reverse (07), Auxiliary Stop (08), 

Keypad Setpoint (09)

None (01)

12

TB-13C Select

None (01), 0-10 VDC (02), 

4-20 mA (03), Preset Speed #3 (04), 

Increase Freq (05), External Fault (06), 

Remote Keypad (07), DB Fault (08), 

Accel/Decel #2 (09), 

Keypad Setpoint (10)

None (01)

14

Control

Terminal Strip Only (01), 

Remote Keypad Only (02), 

Terminal Strip or Remote Keypad (03)

Terminal 

Strip (01)

15

Serial Link

Disable (01), 

9600, 8, N, 2 with Timer (02), 

9600, 8, N, 2, without Timer (03), 

9600, 8, E, 1 with Timer (04), 

9600, 8, E, 1, without Timer (05), 

9600, 8, O, 1 with Timer (06), 

9600, 8, O, 1, without Timer (07),

9600, 8, N, 

2 with Timer (02)

16

Units Editing

Tenths of Units (01), Whole Units (02)

Whole Units (02)

17

Rotation

Forward Only (01), Forward and Reverse (02)

Forward Only (01)

19

Acceleration Time

0.1 - 3600.0 sec

20.0 sec

20

Deceleration Time

0.1 - 3600.0 sec

20.0 sec

21

DC Brake Time

0.0 - 3600.0 sec

0.0 sec

22

DC Brake Voltage

0.0 - 30.0 %

0.0%

23

Min Frequency

0.0 - Max Frequency

0.0 Hz

24

Max Frequency

Min Frequency - 240.0 Hz

60.0 Hz

25

Current Limit

30 - 180%

180%

No.

Parameter 

Name

Range of Adjustment

Factory Default

26

Motor Overload

30 - 100%

100%

27

Base Frequency

25.0 - 500.0 Hz

60.0 Hz

28

Fixed Boost

0.0 - 30.0%

1.0%

29

Accel Boost

0.0 - 20.0%

0.0%

30

Slip Compensation

0.0 - 5.0%

0.0%

31-

37

Preset Speeds

0.0 - Max Frequency

0.0 Hz

38

Skip Bandwidth

0.0 - 10.0 Hz

0.0 Hz

39

Speed Scaling

0.0 - 6500.0

0

40

Frequency Scaling

3.0 - 2000.0 Hz

60.0 Hz

41

Load Scaling

10 - 200%

200%

42

Accel / Decel #2

0.1 - 3600.0 sec

20.0 sec

43

Serial Address

1 - 247

1

44

Password

000 - 999

225

45

Spd at Min Signal

Min Frequency - 999.0 Hz

0.0 Hz

46

Spd at Max Signal

Min Frequency - 999.0 Hz

60.0 Hz

47

Clear History

Maintain (01), Clear (02)

Maintain (01)

48

Program Selection

User Settings (01), OEM Settings (02), 

Reset OEM (03), Reset 60 (04), 

Reset 50 (05), Translate (06)

User Settings (01)

50

Fault History

View Only

(N/A)

51

Software Code

View Only

(N/A)

52

DC Bus Voltage

View Only

(N/A)

53

Motor Voltage

View Only

(N/A)

54

Load

View Only

(N/A)

55

0-10 VDC Input

View Only

(N/A)

56

4-20 mA Input

View Only

(N/A)

57

TB Strip Status

View Only

(N/A)

58

Keypad Status

View Only

(N/A)

59

TB-30 Output

View Only

(N/A)

60

TB-31 Output

View Only

(N/A)

61

PI Mode

Off (01), Normal 4-20 mA (02), 

Normal 0-10 VDC (03), 

Reverse 4-20 mA (04), 

Reverse 0-10 VDC (05)

Off (01)

62

Min Feedback

0.0 - 999.0

0

63

Max Feedback

0.0 - 999.0

100

64

Proportional Gain

0.0 - 99.9 %

5.0%

65

Integral Gain

0.0 - 99.9 sec

0.0 sec

66

PI Accel/Decel

0.0 - 999.0 sec

20.0 sec

67

Min Alarm

0.0 - 999.0

0

68

Max Alarm

0.0 - 999.0

0

69

0-10 VDC Feedback

View Only

(N/A)

70

4-20 mA Feedback

View Only

(N/A)

71

Actual Frequency

View Only

(N/A)

Run/Stop Contact

1

2

5

6

11

12

2

14

13B

13C

Run/Stop Contact

1

2

5

6

11

12

2

14

13B

13C

Speed Pot

Items in 