7
2
.2.3 Setting of Wired C
ontroller’s Address
2
.2.3.1 Enquiry and Setting of Wired Controller
’s Address
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting
interface of wired controller‘s address. In this case, LCD displays address number. Then press▲ or ▼
button to adjust address and then press Enter/ Cancel button to confirm. The address setting is related
to the setting of Debugging Function 4.9.10. When the selection in 4.9.10 is 00, address of centralized
controller is to be set and the address setting range is 01~16; when the selection in 4.9.10 is 01, address
of long-distance monitor is to be set and the address setting range is 01~255.
Enquiry and setting of wired controller‘s address is shown as Figure 2-3-4 below:
Figure 2-3-4 Enq
uiry and setting of wired controller‘s address
2
.2.3.2 Setting of Master/Slave Wired Controller’s Address
Under off status of the unit, press Enter/Cancel and Mode buttons at the same time for 5s to go to
the enquiry and setting interface of master/slave wired controller. In this case, LCD displays wired
controller‘s address (01 for master wired controller and 02 for slave wired controller). Press ▲ or ▼
button to adjust address of master/slave wired controller and then press Enter/Cancel button to confirm.
If slave wired controller is set, the icon
will be displayed.
Note:
If there is only one wired controller, it only can be set as the master. If there are two wired controllers,
one should be the master and the other should be the slave.