Selecting location
10
Special case: ceiling beams
In the case of ceiling beams
measuring > 0.2 m and a total area
of < 36 m², detectors should be
installed in the centre of the room
either on a beam or ceiling panel.
In the case of ceiling beams
measuring > 0.2 m and a total area
of > 36 m², detectors should be
installed in the centre of each
ceiling panel and not on the
beams.