Absolute Process Instruments DuoPak APD 2055 Manual Download Page 2

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

BSOLUTE

ROCESS NSTRUMENTS, Inc.

Instructions 

APD 2055

Calibration

Front-mounted Zero and Span potentiometers for each channel 
can be used to compensate for load and lead variations.
1.  Apply power to the module and allow a minimum 30 minute 

warm up time.

2.  Using an accurate voltmeter on terminals 18 and 20, and 

then 22 and 24, adjust the excitation voltage fine adjust-
ment potentiometers to the strain gauge manufacturer's 
recommended values.

3. Using an accurate calibration source, provide an input to 

the module equal to the minimum input required for the 
application.

4. Using an accurate measurement device for the output, 

adjust the Zero potentiometer for the exact minimum output 
desired. The Zero control should only be adjusted when the 
input signal is at its minimum. This will produce the cor-
responding minimum output signal. Example: for 4-20 mA 
output, the Zero control will provide adjustment for the 4 mA 
or low end of the signal.

5.  Set the input at maximum, and then adjust the Span pot for 

the exact maximum output desired. The Span control should 
only be adjusted when the input signal is at its maximum. 
This will produce the corresponding maximum output 
signal. Example: for 4-20 mA output, the Span control will 
provide adjustment for the 20 mA or high end of the signal.

6.  Repeat adjustments for both channels for maximum accuracy.

Output Test Function

When the Test button is depressed it will drive the output with a 
known good signal that can be used as a diagnostic aid during 
initial start-up or troubleshooting. When released, the output 
will return to normal.
Each Test Cal. potentiometer is factory set to approximately 
50% output. Each can be adjusted to set the test output from 
0 to 100% of the output span. Press and hold the Test button 
and adjust the corresponding Test Cal. potentiometer for the 
desired output level.
They may optionally be externally wired for remote test opera-
tion or a manual override. See wiring diagram at right.

Operation

The APD 2055 accepts two stain gauge inputs and provides 
two optically isolated DC voltage or current outputs that are 
linearly related to the inputs. 
Green LoopTracker

®

 input LEDs provide a visual indication that 

each signal is being sensed by the input circuitry of the module. 
They also indicates the input signal strength by changing in 
intensity as the process changes from minimum to maximum.
If an LED fails to illuminate, or fails to change in intensity as the 
process changes, check the module power or signal input wiring.
Two red LoopTracker output LEDs provide a visual indication 
that the output signals are functioning. They become brighter 
as the input and each corresponding output change from 
minimum to maximum. 
For a current output the red LED will only light if the output loop 
current path is complete. For either current or voltage outputs, 
failure to illuminate or a failure to change in intensity as the 
process changes may indicate a problem with the module 
power or signal output wiring. Note that it may be difficult to 
see the LEDs under bright lighting conditions.

28 Power AC or DC –
26 Earth Ground
25 Power AC or DC +

26

25

27

28

APD 2055

 

Channel 1 

Channel 2 

  Strain Gauge to DC  

Strain Gauge to DC 

  Isolated Transmitter 

Isolated Transmitter

Test Cal.

Span

Zero

Test

Output

Loop
Tracker

Test Cal.

Span

Zero

Test

Output

Input

Loop
Tracker

Loop
Tracker

Input

Loop
Tracker

Channel 1

Channel 2

®

Excitation

Excitation

14

13

15 16

10

9

11 12

External 

Contacts  

for Test 

Function

– 

+ 20V

– 

+ 20V

mA 

Device 2

R

i

mA 

Device 1

R

i

6

5

7

8

2

1

3

4

Current 

Sourcing 

Output

Ch. 1

Ch. 2

Voltage 

Output

– 

+

Voltage 

Device 1

– 

+

Voltage 

Device 2

2

1

3

4

Ch. 1

Ch. 2

6

5

7

8

– 

+

mA 

Device 2

R

i

Loop 

Power 

Source 2

– 

+

+

 –

mA 

Device 1

R

i

Loop 

Power 

Source 1

Current 

Sinking 

Output

Ch. 1

Ch. 2

2

1

3

4

6

5

7

8

+

 –

To maintain full isolation avoid combining power supplies in 

common with inputs, outputs, or unit power.

See manufacturer's 

specifications for 

wiring designations.

Shield wires should 

be grounded at one 

end only.

18

17

19 20

Excitation

 +

Strain 

gauge

Signal 

Excitation

 

22

21

23 24

Excitation

 +

Strain 

gauge

Signal 

Excitation

 

Precautions

WARNING! All wiring must be performed by a qualified electrician 
or instrumentation engineer. See diagram for terminal designa-
tions and wiring examples. Consult factory for assistance. 
WARNING! Avoid shock hazards! Turn signal input, output, and 
power off before connecting or disconnecting wiring, or remov-
ing or installing module.

Précautions

ATTENTION! Tout le câblage doit être effectué par un élec-
tricien ou ingénieur en instrumentation qualifié. Voir le dia-
gramme pour désignations des bornes et des exemples de 
câblage. Consulter l'usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal 
d'entrée, le signal de sortie et l'alimentation électrique avant 
de connecter ou de déconnecter le câblage, ou de retirer ou 
d'installer le module. 

Electrical Connections

Polarity must be observed for signal wiring connections. If the 
input and/or output do not function, check wiring and polarity.
Each product is factory configured to your exact input and 
output ranges as indicated on the serial number label. 

Outputs

For milliamp ranges determine if your devices provide power 
to the current loop or if the loop must be powered by the APD 
module. Typical voltage may be 9-24 VDC at your device's 
terminals if it provides power to the loop.

Bridge Input Channel 1

– Te Terminal

Strain gauge signal input

17 

(

+)

19 (

–)

Excitation voltage

18 (

–)

20 

(

+)

Input 1, Bridge, Strain Gauge, Load Cell

Refer to wiring diagram at right and strain gauge manufac-
turer’s data sheet for wiring and color-coding. Polarity must 
be observed when connecting input. Sensor shield wire (if 
equipped) should be grounded at one end only.
The excitation voltage is factory set and should match the sen-
sor manufacturer's recommendations. A front potentiometer 
allows approximately ±10% fine adjustment of the excitation 
voltage.
CAUTION: Never short the excitation leads together. This will 
cause internal damage to the module.

API maintains a constant effort to upgrade and improve its prod-

ucts. Specifications are subject to change without notice. Consult 

factory for your specific requirements.

Bridge Input Channel 2

– Te Terminal

Strain gauge signal input

21 

(

+)

23  (

–)

Excitation voltage

22 (

–)

24 

(

+)

Input 2, Bridge, Strain Gauge, Load Cell

Refer to wiring diagram at right and strain gauge manufac-
turer’s data sheet for wiring and color-coding. Polarity must 
be observed when connecting input. Sensor shield wire (if 
equipped) should be grounded at one end only.
The excitation voltage is factory set and should match the sen-
sor manufacturer's recommendations. A front potentiometer 
allows approximately ±10% fine adjustment of the excitation 
voltage.
CAUTION: Never short the excitation leads together. This will 
cause internal damage to the module.

Mounting to a DIN Rail

Install module vertically on a 35 mm DIN rail in a protective 
enclosure away from heat sources. Do not block air flow.
1.  Tilt front of module down and posi-

tion the lower spring clips against 
the bottom edge of DIN rail.

2.  Push front of module upward until 

upper mount snaps into place.

Removal

Avoid shock hazards! Turn signal 
input, output, and power off.
1.  Push up on bottom back of module.
2. Tilt front of module downward 

to release upper mount from top 
edge of DIN rail. 

3.  The module can now be removed 

from the DIN rail.

Spring Clips

Upper Mount

Module Power Terminals

Check label for module operating voltage to make sure it 
matches available power. The power supplies are fuse protect-
ed and the unit may be returned to API for fuse replacement.
When using DC power, either polarity is acceptable, but for 
consistency, wire positive (+) to terminal 25 and negative (–) 
to terminal 28.

Device for Output Channel 1

Terminal Terminal

Voltage input device.

3 (

–)

(

+)

Unpowered or passive mA input device.  

APD module provides the loop power.

3 (

–)

(+20 V)

mA input device powers the current loop. 

2 (

–)

(

+)

Device for Output Channel 2

Terminal Terminal

Voltage input device.

7 (

–)

(

+)

Unpowered or passive mA input device.  

APD module provides the loop power.

7 (

–)

(+20 V)

mA input device powers the current loop. 

6 (

–)

(

+)

Cu 60/75°C 

conductors 

14 AWG 

max.

Reviews: