background image

Wiring and Installation 

APD 4058

Settings for Push-Pull Load Cells

The input range can be thought of as a percentage scale. 
Zero percent of the signal range will be a negative number for 
push-pull load cells. The high end of the signal will be a posi-
tive number. Add these together to get the span (100% of the 
total signal range). 
For example, if a load cell has a 1.5 mV/V sensitivity with 10 V 
excitation, the range for push-pull will be –15 mV to +15 mV.
This is a span of 30 mV and we would select 30 mV as our input 
range. If the range does not match up to what is in the table, 
select the next highest input range setting.
For push-pull applications it is common to use a ±5 V or ±10 V 
output setting. Use the table below to find your switch settings.
We also need to use "Offset Switch C" to bring the negative 
end of our input range up by 50% to 0 mV. The closest set-
ting is position "B" 45%. This can be adjusted to 50% with 
the zero potentiometer when output calibration is done. 

M01 Option: Internal Calibration Resistor

The APD 4058 M01 has a user-specified internal calibration 
resistor. A switch on the front of the module allows switching 
of the APD's internal calibration resistor in or out of the circuit. 
The sensor manufacturer should provide the percentage of full-
scale output for the transducer when using the APD's internal 
resistor for calibration. 

M02 Option: Load Cell Calibration Resistor

The APD 4058 M02 has provisions for a load cell with its own 
calibration resistor. A switch on the front of the module allows 
switching of the load cell internal calibration resistor in or out 
of the circuit. 
Refer to the load cell manufacturer's specifications and the 
wiring diagram when connecting a transducer with its own 
internal calibration resistor. 
The transducer's calibration resistor wires are connected to 
terminals 5 and 11 on the APD 4058. 
If the transducer only has one calibration resistor wire, connect 
it to terminal 5.

Input

Refer to strain gauge manufacturer’s data sheet for wire color-
coding and identification. Polarity must be observed when 
connecting inputs.
CAUTION: Do not miswire the load cell and never short the 
excitation leads together. This will cause internal damage to 
the module.

No Sense Leads

When no sense leads are used, jumper terminals 6 and 12.

With Sense Leads

Some bridges or load cells have one or two sense leads. 
Sense leads allow the APD 4058 to compensate for leadwire 
resistance effects. Connect the sense leads if used. Polarity 
must be observed.
Never jumper terminals 6 and 12 when using sense leads.

Output

Polarity must be observed when connecting the signal output.
If your device accepts a current input, determine if it provides 
power to the current loop or if it must be powered by the APD 
module. Use a multi-meter to check for voltage at the device's 
input terminals. Typical voltage may be 9-24 VDC.

Module Power

Check model/serial number label for module operating voltage 
to make sure it matches available power. Connect power last.
When using DC power, either polarity is acceptable, but for 
consistency with similar API products, positive (+) can be wired 
to terminal 13 and negative (–) can be wired to terminal 16. 
CAUTION: To maintain full isolation avoid wiring DC power sup-
plies in common with output and unit power.

Type of Device for Output

– Term.

 + Term.

mA (current) input device that powers 

the current loop. Switch E set to “I”. 

2 (

–)

(

+)

mA (current) input device that is pas-

sive. APD module provides the loop 

power. Switch E set to “I”. 

3 (

–)

(+20 V)

Measuring/recording device accepts a 

voltage input. Switch E set to “V”. 

3 (

–)

(

+)

Mounting to a DIN Rail

Install module vertically on a 35 mm DIN rail in a protective 
enclosure away from heat sources. Do not block air flow. Allow 
1" (25 mm) above and below housing vents for air circulation.
1.  Tilt front of module downward and position against DIN rail. 
2.  Clip lower mount to bottom edge of DIN rail.
3.  Push front of module upward until upper mount snaps into place.

Removal

1.  Push up on the bottom back of the module.
2.  Tilt front of module downward to release upper mount 

from top edge of DIN rail. 

3.  The module can now be removed from the DIN rail.

Spring Clip

Upper Mount

Lower Mount

14

13

15

16

13  Power AC or DC 

+

14 

Earth Ground

16  Power AC or DC –

Module Power

Current sinking output 

switch E set to “I”

External device provides 

power to output loop

2

1

3

4

– 

+

+

 –

Loop 

Power 

Source

+

4-20 mA 

Device

R

i

Current sourcing output  

switch E set to “I”  

+20 V at terminal 4

2

1

3

4

Passive 

4-20 mA 

Device

R

i

– 

+20V

Voltage output  

switch E set to “V”

2

1

3

4

Voltage 

Device

– 

+

Output Wiring

M02 option 

for load cell 

with built-in 

cal. resistor. 

Connect to 

terminals 5 

and 11

No Sense Leads

Jumper 6 to 12 

ONLY if sense leads 

are NOT used

6

5

7

8

10

9

11 12

Strain 

Gauge

Span

Zero

Test

Output

Input

APD 4058

Strain Gauge to DC

Isolated Transmitter

Excitation

V

0

 

+

V

0

 –

V

EX

 –

V

EX

 

+

Exc 

+

Exc –

Sig 

Sig 

+

Test Cal.

Sig 

+

Exc –

Sig –

Exc 

+

Cal.

With Sense Leads

Sense 

+

 

Sense –

Sense 

+

 

Sense –

6

5

7

8

10

9

11 12

Strain 

Gauge

Span

Zero

Test

Output

Input

APD 4058

Strain Gauge to DC

Isolated Transmitter

Excitation

V

0

 

+

V

0

 –

V

EX

 –

V

EX

 

+

Exc 

+

Exc –

Sig 

Sig 

+

Test Cal.

Sig 

+

Exc –

Sig –

Exc 

+

Cal.

M02 option 

for load cell 

with built-in 

cal. resistor. 

Connect to 

terminals 5 

and 11

Colors shown are an example only.  

See manufacturer's specifications for wiring designations.

Shield wires should be grounded at one end only

To maintain full isolation avoid combining power supplies 

in common with input, output, or unit power.

Cu 60/75°C 

conductors 

14 AWG 

max.

1

 2 3 4

5  6 

7  8

9 10 11 12

13 14 

15

 16

Input

Cal. and Sense

Output

Power

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

Wire terminal 
torque 
0.5 to 0.6 Nm or 
4.4 to 5.3 in-lbs

Module powers mA output loop

 * Do not make connections 

to unused terminals!

 * Do not make connections 

to unused terminals!

Summary of Contents for APD 4058 Series

Page 1: ...ges Minimum range 0 to 5 mV Maximum range 0 to 1200 mV Minimum sensitivity 0 5 mV V Maximum sensitivity 120 mV V Millivolt output range is determined by the sensitivity of the sensor mV V and the excitation voltage applied mV V sensitivity X excitation voltage total mV range Input Impedance 1 MΩ typical Common Mode Rejection 100 dB minimum Calibration Resistor Options M01 option Switch with calibr...

Page 2: ...an be set for your application 4 If switch positions are changed repeat the calibration procedure on the last page Precautions Range Setup APD 4058 Output 0 1 V 0 2 V 0 4 V 1 5 V 0 5 V 0 8 V 2 10 V 0 10 V 5 V 10 V 0 2 mA 0 4 mA 0 8 mA 2 10 mA 0 10 mA 0 16 mA 4 20 mA 0 20 mA Switches BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE Input 2 5 mV 1B0V 1B1V 1B2...

Page 3: ...ls Typical voltage may be 9 24 VDC Module Power Check model serial number label for module operating voltage to make sure it matches available power Connect power last When using DC power either polarity is acceptable but for consistency with similar API products positive can be wired to terminal 13 and negative can be wired to terminal 16 CAUTION To maintain full isolation avoid wiring DC power s...

Page 4: ...adjustable from 0 to 100 of the output span Press and hold the Test button and adjust the Test Cal potentiometer for the desired output level Calibration with Resistor Options M01 or M02 Use this calibration procedure if your APD 4058 was ordered with a calibration resistor or if your sensor has its own internal calibration resistor Note Perform the following calibration procedure any time switch ...

Reviews: