background image

Part number 20078, Rev 0 

 

REFRIGERATOR OPERATION 

After the unit is properly installed and power is applied, it will take some time before the 
system is cooled down to temperature and cycling normally. You should wait 8 hours on the 
first startup before beginning to add product to the unit. This ensures that the unit is installed 
and operating properly before being put into service. On subsequent startups (after cleanings, 
for example), this wait time can be reduced to about 3 hours.   After this wait time, the unit 
should be cycling in the desired temperature band. The units are calibrated before leaving the 
factory, so no adjustment should be necessary.  

Loading the units will again cause temperature to rise as the warmer product is introduced into 
the compartment. If a large amount of product is to be introduced, it is a good idea to do it in 
stages, allowing several hours between stages to allow temperature to stabilize again before 
introducing additional warm product. This will minimize the temperature transient while 
loading. Other tips for successful loading include:  

-

 

Leave about 2-3 inches of free space along the back and sides of the unit to allow for proper 
air flow and, therefore, more even cooling of the product.  

-

 

When loading the top shelf, avoid blocking the evaporator fan(s) (if installed). There should 
be at least 4 inches of clearance below the fan(s) to allow proper air flow.  

-

 

Do not overload the unit. Maximum suggested load is about 75% of chamber capacity. 
Additionally, the load should be distributed evenly from top to bottom and side to side for 
best results.  

-

 

Minimize the time the door is open. On top of letting the cold air out, you are also letting 
warm, moist air in which can result in more condensation and/or frost in the unit.  
 

Model ABT-30R will go into a defrost cycle every 6 hours to remove frost build-up around the 
evaporator coils. This cycle can last up to 25 minutes. During this time the compressor is turned 
off and defrost heaters are turned on in the evaporator section. This will cause a rise  in air 
temperature inside the unit but should not significantly affect product temperatures.  

Remember that the units are calibrated to the desired temperature band before leaving the 
factory. We also do extensive testing to ensure that these temperatures will result in product 
temperatures in the desired band. There should be no need to adjust the temperature control 
on these units, but if it is necessary, they can be adjusted using the manual thermostat on the 
inside of the unit

.  

It is STRONGLY RECOMMENDED that you contact the manufacturer’s Technical Support 
Department prior to performing any temperature adjustments to ensure the adjustment is 
necessary and, if so, it is performed correctly.

  

Summary of Contents for ABT-14R

Page 1: ...ery Make sure you get a signed copy Send a written request for an inspection to the carrier B Concealed Damage This type of damage may not be discovered until the unit is being unpacked When concealed damage is discovered stop unpacking immediately and contact the carrier immediately to report the claim and request an inspection This should be done as soon as possible and in any case must be done ...

Page 2: ...ve the unit s model and serial number ready as well as the problem description The model and serial number is located on the serial tag which can be found on the interior left upper wall of the unit For convenience you may want to record the following information here for easy access in the future Model number __________________________________ Serial number __________________________________ Date...

Page 3: ...ry receipt acknowledging the damage This has to happen at the time of delivery or it won t happen at all Keep a copy for your records and send another to the carrier s damage claims department along with a formal request for an inspection report Follow up with a phone call Their contact information can be found on the carrier s web site The second type of shipping damage is concealed damage This t...

Page 4: ... circuit is recommended to prevent possible loss of product due to over loading or failure of other equipment on the same circuit PROTECT THE CIRCUIT WITH A 20 AMP DELAY TYPE FUSE OR CIRCUIT BREAKER Do not use an extension cord Be sure your unit is properly grounded Use the 3 prong plug provided into a 3 prong grounded outlet Only this method complies with national electrical codes local codes and...

Page 5: ...helf clips making sure all corners are seated properly Temperature control NOTE The control is preset at the factory to provide the desired air and product temperatures inside of the unit and requires no further adjustment Please contact us before making any adjustments to determine if adjustment is necessary and if so to make sure it is performed properly These models utilize a manual thermostat ...

Page 6: ...ocking the evaporator fan s if installed There should be at least 4 inches of clearance below the fan s to allow proper air flow Do not overload the unit Maximum suggested load is about 75 of chamber capacity Additionally the load should be distributed evenly from top to bottom and side to side for best results Minimize the time the door is open On top of letting the cold air out you are also lett...

Page 7: ...eplacements are pushed against rear wall or interrupted the proper refrigerator air circulation For the proper air circulation place the products evenly on each shelf Do not push against the refrigerator s rear or side walls Evaporator is blocked by frost or ice Remove the products unplug the refrigerator or freezer power and allow the unit to defrost If the problem still exists call for service 3...

Page 8: ...o prevent leakage Door will not close The unit is not level Refer to the Leveling section at the beginning of this manual Check for dirt and debris or items passing through the door seal MOISTURE DURING THE SUMMER SEASON The amount of moisture condensation or high humidity related issues increase during the summer and in most cases will self resolve when the weather cools down Please note a refrig...

Page 9: ...s water out of sponge or cloth before cleaning around controls light bulb or any electrical parts Glass Doors if applicable Soap and water Clean the glass with a mild detergent and water on a soft cloth or sponge Rinse with water and wipe dry Door Gaskets Soap and water Wipe gaskets and their seating surfaces with a clean soft cloth Shelves Soap and water Do not wash removable shelves in dishwashe...

Page 10: ...TY In addition to the two 2 year warranty stated above Horizon Scientific Inc warrants its hermetically and semi hermetically sealed compressors to be free from defects in both material and workmanship under normal use and service for a period of three 3 additional years from the end of the initial two 2 year warranty period but not to exceed five 5 years after shipment from Horizon Scientific Inc...

Page 11: ...ood or other external causes It does not apply to defects resulting from failure to properly install operate or maintain the product in accordance with the printed instructions provided or damage caused by the storage of any corrosive material that comes in contact with the interior or exterior portions of the cabinet or the use of spark producing equipment or containers such as galvanized or carb...

Reviews: