Above
Air
™
MissionCritical
™
A/C’s
AboveAir
Technologies
(MC22-L12)
16
Guide Specifications
Guide Specifications -
MC
-
2x2
™
Mission
Critical
(1-3 Tons)
2.5 Accessories
2.5.1 Plenum Discharge Box
(UF - Up-Flow Units)
A (2-way, 3-way or ducted) plenum
discharge box shall be provided for field
installation to the top of the up-flow unit.
The plenum box shall be 18.5 inches
high, insulated and powder-coat painted
to match the color of the unit.
2.5.2 Floor Stand
A ____ inch high floor stand shall be
factory provided for field installation. The
floor stand shall have adjustable legs
with vibration isolation.
2.5.2.1 Turning Vanes
Turning vanes shall be factory provided
with the floor stand to direct the dis
-
charge air either to the front or rear of
the unit.
2.5.3 Condensate Pump
(Factory Installed - UpFlow)
A condensate pump shall be factory
provided and installed within the indoor
evaporator section
(Up-Flow Air Pattern
Configurations)
. The condensate pump
shall be provided with dual internal float
switches: one for pump operation initia
-
tion and the other for pump reservoir
overflow safety.
(
Note:
Down-Flow unit Condensate Pump
Option requires field installation of the pump
outside of the A/C unit. A condensate pump
fused power supply terminal connection
shall be factory provided within the A/C unit
evaporator.)
2.5.4 Hot Gas Bypass Systems
2.5.4.1 Hot Gas Bypass To
Evaporator Inlet
Each refrigerant circuit shall be pro
-
vided with a factory installed hot gas
(discharge) bypass valve. The hot gas
bypass valve shall be designed to supply
hot gas to evaporator inlet as required to
provide coil freeze-protection and capac
-
ity modulation under low load conditions.
2.5.4.2 Hot Gas Bypass To
Suction Line with
Quench Valve
(VCH/XPU-CCU/CWU-CGU
Remote Condensing Units
3
rd
Line Not Required!)
Each refrigerant circuit of the Split DX
system shall be provided with a fac
-
tory installed hot gas bypass system to
include: hot gas (discharge) bypass and
desuperheating quench. The hot gas
bypass system shall be designed to sup
-
ply hot gas and liquid refrigerant to the
suction line as required to provide coil
freeze-protection and capacity modula
-
tion under low load conditions. All hot
gas bypass components shall be factory
installed and shall not require additional
field refrigerant lines on split DX sys
-
tems.
2.5.5 Suction-Line Accumulator
Each refrigerant circuit shall be provided
with a factory installed Suction-Line Ac
-
cumulator to prevent liquid slugging of
the compressor and excessive refriger
-
ant dilution of the compressor oil during
low load conditions. The accumulator
shall return refrigerant and oil to the
compressor at a sufficient rate to main
-
tain both system operating efficiency and
proper oil level. The accumulators shall
be wrapped with a 1/2” closed-cell neo
-
prene insulation to prevent sweating.
2.5.6 Main Power, Non-Fused
Disconnects
(Remote Condenser Section)
The remote condensing unit (or con
-
denser) shall be factory provided with
a main power non-fused disconnect for
field installation. The disconnect shall be
NEMA rated for indoor or outdoor instal
-
lation as required.
2.5.7 Firestat
(Factory Installed)
A Firestat shall be factory installed in the
return air stream of the unit and wired to
the A/C unit electrical control panel. The
Firestat shall shut-down all A/C system
operations upon sensing a high return air
temperature condition.
2.5.8 Smoke Detector
(Factory Installed)
A Smoke Detector shall be factory
installed in the return air stream of the
unit and wired to the A/C unit electrical
control panel. The Smoke Detector shall
shut-down all A/C system operations
upon activation.
2.5.9 Remote Water-Leak
Detector
A remote water-leak detector shall be
factory provided for field installation. The
remote water-leak detector shall be wired
to shut down all A/C unit water producing
functions upon sensing a water leak.
2.5.10 Flow Switch -
Water/Glycol Condenser
A factory installed flow switch shall
shut-down / lockout compressor opera
-
tion prior to the high refrigerant pressure
switch alarm upon sensing a loss or low
dx condenser water/glycol flow. A flow
switch alarm shall be indicated both via
MC-2000 microprocessor display and
auxililary dry-contact terminal connec
-
tion.
2.5.11 Compressor Acoustic /
Sound Jacket
Each compressor shall be provided with
a factory installed compressor sound
jacket with snap closure system for ease
of removal and reinstallation. Sound
jackets shall have a noise reduction coef
-
ficient (NRC) of 85 per ASTM and C-423
and a sound transmission lost (STC) of
11 per ASTM E-90.