background image

REV 0.0 April 18, 2023 

 

 

Page 3 

 

Shielding 

Shielding is required for all Gateway-connected cables. See the Appendix for identification by ABM model number of 
the sensors discussed in the following shielding rules: 

 

Most important: the shield shall be connected to earth-ground in only one location. Connections at multiple 
points will create a ground-loop that can result in significant ground differential voltages and currents, which 
can adversely affect communication and even damage installed equipment. 

 

Ideally, the sole earth-ground connection to the system’s cable shield should be made at either end (as 
opposed to somewhere in the middle) of a multi-drop cable run. In most cases, especially if a line-powered 
DC supply is used, it is best to ground it at the power supply. 

 

The shields of all low-voltage cables should be connected together. Twisting together is acceptable, but 
screw terminals, wire nuts or soldered connections are more reliable. 

 

The installer must prevent the bare shield wires from touching any metal housing or any other conductors. 

 

AC powered sensors must have an earth-ground wire directly connected to Terminal 6 for electrical safety as 
part of the AC supply. Terminal 6 is internally connected to Terminal 3 on all sensors. Therefore, the cabling 
system shield can use Terminal 3 on one AC sensor as its grounding point – as long as it is not already 
grounded elsewhere. 

 

DC powered sensors are not required to have an earth-ground wire connecting to Terminal 3 or 6, as low-
voltage installation rules do not require such. However, DC sensors with metal housings may be indirectly 
grounded through their mounting – for instance, where a metal or otherwise conductive tank is grounded to 
earth through its base and the sensor is installed without an isolating mount such as an aiming device. If a DC 
sensor is not indirectly grounded in this manner, nor grounded through an earth-ground wire connected to 
either Terminal 3 or 6, then the system shield wire should be connected to Terminal 3 or 6. 

The above shielding rules are illustrated throughout the configuration examples in Section D. 
 

RS485 Common Connection 

While it is common practice to implement RS485 wiring with only two wires (“A” and “B”), this is risky over long 
distances and multiple network nodes. Best practice, per the RS485 standards, is to provide a Common connection 
between nodes.  

The Gateway’s Common connection is the black wire of the red/black pair of both pigtail cables. The white/black pair 
of the 2-pair cable provides the A/B connections. 

For sensors that are not powered through the Gateway, such as AC powered sensors, the Common connection is to be 
made through Terminal 4, which is Common for both the RS485 and the mA loop current output. For all DC powered 
sensors, Terminal 4 connects internally to Terminal 7 (labelled “L2/N”). 

 
RS485 Network Initialization 

ABM sensors are supplied with a factory-default SID = 2, unless they were specifically ordered from ABM for a 
Gateway network configuration with a pre-assigned Serial ID (SID) sequence. The connection of more than one sensor 
having the same SID will result in communications failure. 

Therefore, installation of more than one factory-default sensor to the Gateway requires that the installer only add one 
sensor at a time to the RS485 bus (the black/white twisted pair) to re-assign its SID to a unique number, as described 
in the Cellular Gateway User Manual. 

 

 

Summary of Contents for ABM300-CGC4

Page 1: ...is weak For such locations it is highly recommended that the installer determine an optimal mounting location by using a cell phone display to assess the signal strength The standard antenna supplied...

Page 2: ...n box is required to connect it to the RS485 and DC power buses It is not necessary to install the Gateway at one end of the RS485 bus as shown in several examples in Section D it can be located anywh...

Page 3: ...grounded through their mounting for instance where a metal or otherwise conductive tank is grounded to earth through its base and the sensor is installed without an isolating mount such as an aiming...

Page 4: ...ateway is not supplying sensor power the red wire is either cut off or insulated with tape inside the sensor The black wire from the red black pair is still connected to provide a signal common for th...

Page 5: ...ing earth grounded at the sensor since being AC powered Terminal 3 must be earthed through Terminal 6 Optionally the shield could be earth grounded at the junction box but not at the sensor or power s...

Page 6: ...the sensor is mounted on a non metallic tank or uses a sensor aiming mount that electrically insulates the housing from earth ground Figure 3 Simple DC Sensor Connections No Current Output Note that i...

Page 7: ...eld wire should not connect to either Terminals 3 or 6 in that sensor However the shield wire is connected to the upper isolated sensor In multiple sensor configurations powered by the Gateway the vol...

Page 8: ...re powered directly from the 24Vdc supply It is shown as a separate power supply but one could use a 24Vdc supply from the PLC instead In either case the Sensor Supply output from the Gateway is not c...

Page 9: ...through its mounting configuration caution required re shield wire may be powered from the Gateway sensor power output AC Radar ABM400 xxxYYC4 series and ABM430 xxxYYC4 series should be earth grounde...

Reviews: