4.4.  Operation 

 

4.4.1.  LED panel (Standard) 

 

4.4.1.1  Start Up in Normal AC Mode   

 

1.  Before commencing the installation, please ensure the grounding is 

connected properly. 

2.  Ensure the voltage of Utility matches with the input voltage window of the 

UPS. 

3.  Connect UPS main power cord into Utility AC power source receptacle. 

4.  Switch on the AC power source, Press the ‘

’ Switch to start the UPS   

for approximately 3 seconds until the buzzer beeps, the LED display of "

 

" and" 

" will light up after 30 seconds. The start-up procedure is 

completed and the UPS outlets are ready to supply to load. 
 

It is advisable to perform a battery mode test before connecting the loads to 
the UPS to ensure the batteries are working properly. 
Switch Off the AC power source when the UPS had been switched on. The 

  LED on the front panel display will light off while the 

  LED will be 

illuminated and the buzzer alarm will beep intermediately, indicating the UPS 
is in Battery Mode. Connect a non critical load to the UPS outlets to confirm if 
the Battery is supplying power. Repeat the test by switching on & off the AC 
power source to ensure the UPS is functioning properly 

 

4.4.1.2  Start-up in Battery Mode (Cold Start) 

 

This UPS is able to be Switch On for operation without the presence of an 

AC power source. 

 

Press and hold the ‘

’ Switch until the buzzer beep, within the next 10 sec 

press and hold the ‘

’ Switch for 2

nd

 time. The UPS shall perform its start-up 

procedure. The LED display of "

 " and" 

" will light up after 30 

seconds, the buzzer will beep intermediately to indicate successful power on. 

 

Note: *Ensure the UPS Battery is pre-charge for minimum 4 hours by simply 

connecting the AC power cord to the Utility receptacle. 

Summary of Contents for MSRT-Pro 1KVA

Page 1: ...n 17 4 1 Unpacking 17 4 2 Selecting Installation Position 18 4 3 Set up 19 4 4 Operation 23 5 UPS Working Principle 36 5 1 UPS System Block Diagram 36 5 2 When Utility is Normal 37 5 3 When Utility is...

Page 2: ...all ventilation openings free from obstruction and do not place anything on top of the UPS Keep the UPS rear panel 20 cm away from the wall or other obstructions 8 The battery will discharge naturally...

Page 3: ...ion even in the most difficult of environment with space constraints 2 This UPS is equipped with fully digitalized control logic for greater functionality and enhanced high level of power protection D...

Page 4: ...o indicate there is an output available at the Programmable Outlet 1 Programmable Outlet 2 Amber LED lights up to indicate the Bypass Input is normal UPS Fault LED UPS On Alarm Silence UPS OFF Switch...

Page 5: ...n Service Mode 7 OFF UPS Shutoff 8 FAIL UPS Abnormal Lock 9 UPS Flow Chart 10 4 Digits Measurement Display 11 Indicate the item desired to be measured 12 Er05 Battery Weak or Dead 13 Er06 Output Short...

Page 6: ...put circuit breaker for two programmable outlets 230V 1 1 5KVA 2KVA 3KVA 11 3 3 Operating Modes Voltage System Configurations Download and open the UPS Setting Tool Software to see the screen as below...

Page 7: ...y existing after setting is complete 3 seconds later reconnect input power cord into AC Power Utility receptacle and turn on the UPS referring to the section 4 4 Operation The UPS will perform in new...

Page 8: ...e to shutdown whole unit without internal power supply existing after setting is complete 3 seconds later reconnect input power cord into AC Power Utility receptacle and turn on the UPS referring to t...

Page 9: ...ation Read the Safety Instruction guide page 2 to 3 before installing the UPS 4 1 Unpacking Inspect the UPS upon receipt The manufacturer designed robust packaging for your product However accidents a...

Page 10: ...arance from the rear panel of the UPS to avoid any obstructions 2 Do not block the air flow to the ventilation louvers of the unit 3 Please ensure the installation site is free from excessive dust and...

Page 11: ...20 Power Module Battery Module Step 1 Step 2 A4 S1 21 Rack Mount Configuration Setup Step 1 Step 2 Step 3...

Page 12: ...er source when the UPS had been switched on The LED on the front panel display will light off while the LED will be illuminated and the buzzer alarm will beep intermediately indicating the UPS is in B...

Page 13: ...inated when the self test is completed without finding any faults or abnormal conditions The LED will automatically lights off 30 sec after the successful self test 4 4 2 LCD panel Optional 4 4 2 1 St...

Page 14: ...he LCD display illustrates from drawing G to drawing H then the UPS will be in self test Mode The UPS may offer energy to the output in a minute and the LCD display illustrates as drawing I In case of...

Page 15: ...ng P1 P1 P2 2 Press key pad to scroll down the LCD screen then check the UPS settings The LCD display will show in sequence Drawing P1 buzzer Drawing Q1 self test Drawing R1 Bypass Voltage Drawing S O...

Page 16: ...Q2 all the rest default settings may be changed by pressing scroll up key pad 4 Drawing R1 and R2 mean the bypass input acceptable window it can be 180Vac 260Vac for 220Vac system 90Vac 130Vac for 11...

Page 17: ...zer will sound twice d Turn off the Breaker of the Utility Input e The UPS lock problem is solved now 33 4 4 2 7 Shut Off 1 Press key pad for about 5 seconds the Inverter output will be turned off the...

Page 18: ...34 4 4 4 Battery Replacement Step 1 Step 2 35 Step 3 Step 4 1 1 5KVA 2K 3KVA...

Page 19: ...d Utility Abnormal under or over voltage Absent Rectifier and charger stop operating Battery discharge via DC DC boost circuit and supply to Inverter Loads continue to receive supply from Inverter Ala...

Page 20: ...after a preset threshold to avoid the battery from over drain The Battery Low LEDs will light up till the UPS is completely cut off The UPS will re start automatically when Utility is available Fig 5...

Page 21: ...temperature If the UPS experiences internal over temperature when Utility is normal it will switch to bypass loop The UPS will switch back to inverter mode when the over temperature situation is elimi...

Page 22: ...e has been wrongly wired or if the Ground Neutral Voltage exceeded the limits 5 Verify if the ventilating fans are functioning properly Do not attempt to replace the fans by yourself Contact your loca...

Page 23: ...tery Disconnect Er28 Bypass overload Er31 EEPROM s data not conform to the Jumper Setting 45 6 3 Maintenance Clean the dust from the ventilation openings and intakes on the rear panel 1 Turn off the U...

Page 24: ...2 cable is provided with the UPS USB cable is optional 7 2 Software Installation Please refer to the user s manual of the bundled software CD_ROM for installation guide EPO G DC 36V AC OUTPUT 2 1 47 8...

Page 25: ...al Slot 8 3 5 Flexible signal output for N C Normal Close or N O Normal Open contact by shorting pin1 2 or pin2 3 form JP1 5 8 3 6 The shutdown function will be enabled in 1 minute after blackout occu...

Page 26: ...Regulation 1 until low battery warning Output INV mode Frequency Synchroniz ed Range 3Hz or 1Hz setting by software 51 Frequency Battery Mode 0 1 0 05 0 06Hz unless synchronized to line PF 0 7 3 1 Cu...

Page 27: ...nce every 1 5 seconds Low Battery Sounding once every 0 2 seconds Overload Sounding once every 3 second Fault Continuously Sounding or Sounding once every 3 second 53 Physical Dimensions HxWxD in mm 8...

Page 28: ...54 55 192321132048001...

Reviews: