background image

 

REPLACING THE BATTERY

 

Note

Once the battery is disconnected, the loads are not protected 

from power outages. 
1. 

Use an insulated philip screwdriver to remove the four screws located   
at the base of the UPS.   

2. 

Remove the front panel and top cover. 

3. 

Use an insulated philip screwdriver to remove the two screws from the 
battery holding plate. (for 1500L/1800L/2200L only) 

4. 

Disconnect the battery cable terminals before removing the battery    from 
the UPS. 
Step1: Loosen the black cable from the negative (-) terminal. 
Step2: Loosen the red cable from thepositive (+) terminal. 

5. 

Connect the battery cables to the terminals of thenew battery. 
Step1: Insert the black cable to the negative (-) terminal. 
Step2: Insert the red cable to thepositive (+) terminal. 

Note: Small sparks at the battery connectors are normal during connection. 

6. 

Slide the battery into the UPS. 

7. 

Use an insulated philip screwdriver to fasten the two screws on the battery holding plate. (for 1500L/1800L/2200L 
only) 

8. 

Close the front panel and fasten the four screws located at the base of the UPS. 

9. 

Dispose off the old battery properly at an appropriate recycling facility. 

 

 

 

 

 

TROUBLESHOOTING

 

Refer to the steps below should the UPS fail to 
function correctly   
 
Step 1: Is the AC Mains switch in the “ON” 
position? 
Step 2:Is the UPS plugged into the AC power 
supply? 
Step 3: Is the power supply within specified unit 
values? 
Step 4: Has the fuse gone in the mains plug? 
Step 5: Is the UPS overload? 
Step 6: Is the battery flat or defective?

 

Situation 

Problem / Possible Causes 

Solution 

No LEDs display on the front panel.

 

Battery voltage is low. 

Charge the UPS at least 6 hours. 

Battery is defective. 

Replace the battery with the same capacity. 

The UPS is not turned on. 

Press the power switch again to turn on the UPS. 

Alarm beeps continuously when 

the Utility is normal.

 

The UPS is overloaded.

 

Remove some loads/equipment first. The connected equipment exceeds the   
UPS specified ‘capacity/load”. 

UPS does not provide   
expected backup time.

 

The UPS is overloaded. 

Remove some loads/equipment first. The connected equipment exceeds the   
UPS specified ‘capacity/load”. 

Battery voltage is too low. 

Charge the UPS at least6 hours. 

Battery is defective.   

Replace the battery with the same capacity. 

The Utility is normal but LED   

is flashing.

 

Power cord is loose.

 

Reconnect the power cord properly.

 

 

 

 

 

Description 

Ablerex GR600/GR800 SPECIFICATIONS 

Ablerex GR1200/GR1800/GR2000 SPECIFICATIONS 

Model 

GR600 

GR800 

GR1200 

GR1800 

GR2000 

Input 

Voltage 

220/230/240VAC 

Voltage Range 

160~290Vac 

Output 

Voltage Regulation 

+/- 10% 

Transfer Time 

Typical 2-6ms, 10 ms max. 

Waveform 

Simulated Sine Wave 

Battery

 

Type & Number 

12V/7Ah x 1 

12V/9Ah x 1 

12V/7Ah x 2 

12V/7Ah x 2 

12V/9Ah x 2 

Charging time 

4-6 hours recover to 90% capacity 

Physical 

Dimension (WxHxD, mm) 

100 x 140 x 292 

148 x 198 x 315 

Net Weight (kg) 

5.5 

11 

12 

Packaging Dimension 
(WxHxD,mm) 

137 x 226 x 321 

229 x 302 x 411 

Gross Weight (kg) 

5.5 

12 

13 

Environment

 

Humidity 

0-90 % RH @ 0-40 C (non-condensing) 

Noise level 

Less than 40 dB 

  Certification 

  Safety Standard 

EN62040-2 

  EMC/Surge Standard 

EN61000-3-2, EN61000-3-3 

  Mark 

CE, RoHS, TISI 

 

GR600/GR800

 

GR1200/GR1800/GR2000

 

STEP1

STEP2

STEP1

STEP2

192321982006000

 

Reviews: