21
35
Battery equalized time
60min (default)
Setting range is from 5min to 900min.
Increment of each click is 5min.
36
Battery equalized timeout
120min (default)
Setting range is from 5min to 900 min.
Increment of each click is 5 min.
37
Equalization interval
30days (default)
Setting range is from 0 to 90 days.
Increment of each click is 1 day
39
Equalization activated
immediately
Enable
Disable (default)
If equalization function is enabled in program 33, this program
can be set up. If “Enable” is selected in this program, it’s to
activate battery equalization immediately and LCD main page
will shows “
”. If “Disable” is selected, it will c
ancel
equalization function until next activated equalization time
arrives based on program 37
setting. At this time, “
” will
not be shown in LCD main page.
Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable
information is switched as the following table order
.
Selectable information
LCD display
AC Input 1 voltage/ AC output 1 voltage
(Default Display Screen)
AC Input 1 Voltage=120V, AC output 1 voltage=120V
AC Input 2 voltage/ AC output 2 voltage
AC Input 2 Voltage=120V,AC output 2 voltage=120V