Mechanical and electrical installation
16
2
Install the energy meter on a DIN rail in the
distributor.
y
The distance to the current transformers is
determined by the connection cables of the
transformers.
3
Locate the cables for current measurement in the
distributor.
4
Connect the energy meter to the mains via specially
fused cable taps (F = 315 mA).
y
Assign the screw terminals
7
,
8
,
9
and
!
on the energy meter in accordance with the
connection mode selected ( page 14).
F
5
Connect the fixed connection cables of the current
transformers to the energy meter.
y
Assign the connection terminals
1
,
2
,
3
,
4
,
5
and
6
on the energy meter in accord-
ance with the connection mode (see table next
page).
K
L
K
L
K
L