Taking the Wallbox eM4 Twin out of operation |
51
Taking the Wallbox eM4 Twin out of operation
In case of severe malfunctions or damage to the device, you must take the Wallbox eM4 Twin out of operation. To do
so, proceed as follows:
1
Open your domestic power distribution box, discon-
nect the power supply cable from the electricity grid
via the MCB, secure the MCB against being switched
on again and close the distribution box.
• The Wallbox eM4 Twin is now powered off.
1
0
2
Unlock the side RCCB flaps using the key supplied
and flip them up.
3
In addition, flip the pivot levers of both RCCBs to the
0
position.
1
0
1
+
0
4
Close the RCCB flaps again and lock them with the
key.
The Wallbox eM4 Twin can now be dismantled by a qualified specialist electrical contractor if necessary.
DANGER!
Dangerous electrical currents
Note that the Wallbox eM4 Twin is only powered off when the upstream MCB in the domestic power distribution
is switched off (position
0
). The wallbox’s two RCCBs only disconnect the power modules from the mains, but the
internal electronic components remain connected to the mains.
DANGER!
Dangerous electrical currents
Always make sure the supply cable is voltage-free before you start dismantling the wallbox.