Isolated Digital Inputs 

General Description 

Inactive, LED off 

Active, LED on 

Maximum 

Resistance 

Positive voltage-activated  0~+1.8V 

+4.5~36.0V 

±60V DC 

12kΩ to GND 

COM

-VE

D.INs

Digital Inputs

COM

-VE

1

0

8

9

DRY 

CONTACTS

(EG. RELAY
CONTACTS
SWITCHES)

FIELD 

SUPPLY

    

Inputs 0~3 can be used for Pulse Counts. Max count rate <= 50Hz 

 

 

Analog Inputs 

General Description 

Inactive, LED off 

Active, LED on 

Maximum 

Resistance 

Positive 4~20mA current 

0~+4mA 

+4~20mA 

±5V ±40mA 

120Ω to GND 

GND

A.INs

4~20 mA

TRANSDUCERS

Analog Inputs

3

1

2

0

FIELD 

SUPPLY

 

IG-671-2.2-2015-Mar 

Installation Guide

Summary of Contents for Topcat TC0

Page 1: ...Models TC0 TC1 and TC3 Installation Guide ...

Page 2: ... Rating 11 36V DC 1 5A 12V DC 0 75A 24V DC DC Supply External Load 11 36VDC POWER 11 36V DC SUPPLY 12V SW 12V LOAD An external power option can be installed in Topcat that can provide a switched 13 8V supply up to 1A through pins 2 and 3 of the power connector as shown This can be used to power an external device such as a cellular modem Connect an antenna before powering up Topcat Depth is 125mm ...

Page 3: ...nputs COM VE 1 0 8 9 DRY CONTACTS EG RELAY CONTACTS SWITCHES FIELD SUPPLY Inputs 0 3 can be used for Pulse Counts Max count rate 50Hz Analog Inputs General Description Inactive LED off Active LED on Maximum Resistance Positive 4 20mA current 0 4mA 4 20mA 5V 40mA 120Ω to GND GND A INs 4 20 mA TRANSDUCERS Analog Inputs 3 1 2 0 FIELD SUPPLY IG 671 2 2 2015 Mar 2 Installation Guide ...

Page 4: ...gital Outputs COM LOAD LOAD 6 A MAX PER OUTPUT FIELD SUPPLY Security I O The fail safe alarm is an open collector which can carry 50mA up to 30V and can drive a relay coil directly INHIBIT TAMPER ALARM GND Door Switch Key Operated Switch Fail safe Alarm see text Security I O SECURITY I O Installation Guide 3 IG 671 2 2 2015 Mar ...

Page 5: ...t This is a standard 100 base T Ethernet port which is operational when the appropriate firmware is installed External Radio Connections These connections are applicable only when no internal radio is fitted 1 8 RJ45 Pins Always use best radio frequency engineering practices for all radio and antenna installation Dir Name 1 sf 12V 2 2 1 sf COut2 3 1 sf CIn2 4 sf COut1 5 sf CIn1 6 sf TxD 7 sf RxD 8...

Page 6: ...g on the radio channel TX DATA Yellow Shows the data being transmitted by Topcat A short blink is about 0 1 seconds A long blink is about 0 5 seconds Ready LED and Reset Ready LED indication swampfox operating state Green Normal Topcat is operating normally Red Defect Hardware or firmware fault The RESET button is behind a small unmarked hole in the front panel near the DISPLAY button To reset and...

Page 7: ...Notes IG 671 2 2 2015 Mar 6 Installation Guide ...

Page 8: ...x 27 497 Wellington New Zealand Phone 64 4 385 6611 Fax 64 4 3856848 Document number IG 671 2 2 2015 Mar Products Covered TC0 TC1 and TC3 all variants Revision Number 2 2 Revision date 15 March 2015 Topcat and the logo are trademarks of Abbey Systems Ltd registered with the U S Patent and Trademark Office ...

Reviews: