Fig. 2.3.5.1.3 Earthing
of the circuit in the low
voltage compartment
—
Fig. 2.3.5.1.4 Earthing
the circuit on the
terminal board of a
transformer
Earthing of open delta windings
If the open delta windings of the voltage
transformers are damped with a resistor, the
windings connected in an open delta are to be
earthed at one point. The circuit can be earthed.
•
In the low voltage compartment (Fig.2.3.5.1.3)
or.
•
On the terminal block of a voltage transformer
(Fig.2.3.5.1.4).
Perform measurements to ascertain which earthing
method applies to your system.
Remove the earthing wire of the open delta
windings from the terminal boards of the
voltage transformers in accordance with
the circuit diagrams (Fig.2.3.5.1.5) or
earth the open delta windings using the
earthing wire (Fig.2.3.5.1.6).
Earth the circuit at one point only.
Checking the wiring
Finally, check the earthing system of the
voltage transformer wiring in accordance
with table 2.3.5.1.1.