ABB | SACE Tmax XT
Ekip Touch - Measurements | 1 - Standard Measurements
111 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Min-Max measurements
Ekip Touch records the maximum and minimum phase currents in the
Measurements
-
Historicals
-
Measurements
menu
The recording interval between one measurement and the next can be set via the Monitor time parameter,
available in the
Settings
menu (page 37).
Representation
Select one of the measurements to access the graph page containing the records
Each measurement allows up to 25 recordings, each shown in a bar chart (graphic full scale equal to 125%
of the rated value).
The selected recording flashes, to distinguish it from the others.
Touch the sides of the display to select the recordings after (
1
) and before (
2
) the selected recording. The
command for quitting the page (
3
) is in the top left corner.
The selected recording flashes, to distinguish it from the others.
• time elapsed from previous measurement
• phase and value of measurement
• date and time of recording
NOTES:
•
if the value is less than the minimum viewable threshold, “…” is indicated instead of the value
•
graphic representation is in relation to 1 In, with 1.25 In as maximum value
•
the trip unit immediately makes a recording when the “Monitor time” parameter is changed
Reset measurements
The Reset measurements command is available in the
Measurements
-
Historicals
-
Measurements
menu, for
the purpose of resetting all the recordings