Cos
ϕ
Rated current
Breaking capacity
220 V AC
0.7
2.5 A
25 A
380 V AC
0.7
1.5 A
15 A
500 V AC
0.7
1.5 A
15 A
660 V AC
0.7
1.2 A
12 A
Time constant
24 V DC
1 ms
10 A
12 A
15 ms
10 A
12 A
50 ms
8 A
10 A
200 ms
4 A
7.7 A
60 V DC
1 ms
8 A
10 A
15 ms
6 A
8 A
50 ms
5 A
6 A
200 ms
4 A
5.4 A
110 V DC
1 ms
6 A
8 A
15 ms
4 A
5 A
50 ms
2 A
4.6 A
200 ms
1 A
2.2 A
220 V DC
1 ms
1.5 A
2 A
15 ms
1 A
1.4 A
50 ms
0.75 A
1.2 A
200 ms
0.5 A
1 A
Note
With the set of 10 auxiliary contacts supplied as standard, the following are available:
– 3 NO co 5 NC contacts for fxed circuit-breakers
– 3 NO co 4 NC contacts for withdrawable circuit-breakers
With the set of 15 auxiliary contacts (+5 contacts on request compared to the 10 sup -
plied as standard), the following are available:
– for fixed circuit-breaker, as desired, 6 NO co 7 NC contacts or 5 NO con -
tacts + 8 NC contacts or 3 NO co 10 NC contacts
– for withdrawable circuit-breakers, depending on the applications required, a maxi -
mum of 6 NO co 6 NC contacts and a minimum of 5 NO co 5 NC
contacts are available.
Locking magnet on the truck (-RL2)
Un
24 - 30 - 48 - 60 - 110 - 125 - 127 - 132 - 220
- 240 V–
Un
24 - 30 - 48 - 60 - 110 - 125 - 127 - 220 -
230 ... 240 V~ 50/60 Hz
Operating limits
85 … 110% Un
Inrush power (Ps)
W;
DC = 250
AC = 250 VA
Continuous power (Pc)
DC = 5 W; AC = 5 VA
Inrush time
150 ms
Motor operator (-MS)
Characteristics
Un
24...30 - 48...60 - 110...130 - 220...250 V–
Un
100...130 - 220...250 V ~ 50/60 Hz
Operating limits
85 … 110% Un
≤
40 kA
Inrush power (Ps)
DC=600 W; AC=600 VA
Rated power (Pn)
DC=200 W; AC=200 VA
Inrush time
0.2 s
Charging time
6-7 s
Insulation voltage
2000 V 50 Hz (for 1 min)
Auxiliary contacts of the circuit-breaker
Rated insulation voltage
according to VDE 0110, Group C
660 V AC
800 V DC
Rated voltage
24 V... 660 V
Insulation-test test voltage
2.5 kV
Maximum rated current
10 A
Number of contacts
5
Stroke
6 mm ... 7 mm
Contact force
26 N
On resistance
3 m
Ω
Storing temperature range
- 20° C ... + 120 °C
Operating temperature range
- 20° C ... + 70 °C
Contact over temperature
20 K
Operating cycles
30,000
Unlimited short circuit stability by using fuses of max. 10 A time-lag
13