Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
39
7.1.3 IECEx
Designation:
Ex ia IIC T6 or T4 Gb
Ex ib IIC T6 or T4 Gb
Ex nA IIC T6 or T4 Gc
Certificate No.:
IECEx TUN 04.0015X
Issue No.:
5
Type:
Intrinsic safety "i" or "n" type of protection
Standards: IEC
60079-0:2011
IEC 60079-11:2011
IEC 60079-15:2010
Type and
designation
TZIDC Ex ia IIC or Ex ib IIC
Temperature class
Ambient temperature range
T4
-40 ... 85 °C
-40 ... 85 °C
T6
1)
-40 ... 40 °C
-40 ... 50 °C
1) When using the "digital feedback" plug-in module in temperature class T6, the maximum permissible ambient
temperature range is -40 ... 35 °C.
Summary of Contents for TZIDC
Page 46: ...Ex relevant specifications 46 TZIDC TZIDC 110 TZIDC 120 CI TZIDC 110 120 EN...
Page 47: ...Ex relevant specifications CI TZIDC 110 120 EN TZIDC TZIDC 110 TZIDC 120 47...
Page 48: ...Ex relevant specifications 48 TZIDC TZIDC 110 TZIDC 120 CI TZIDC 110 120 EN...
Page 57: ...Ex relevant specifications CI TZIDC 110 120 EN TZIDC TZIDC 110 TZIDC 120 57...
Page 58: ...Ex relevant specifications 58 TZIDC TZIDC 110 TZIDC 120 CI TZIDC 110 120 EN...
Page 67: ...Ex relevant specifications CI TZIDC 110 120 EN TZIDC TZIDC 110 TZIDC 120 67...
Page 68: ...Ex relevant specifications 68 TZIDC TZIDC 110 TZIDC 120 CI TZIDC 110 120 EN...
Page 70: ...Appendix 70 TZIDC TZIDC 110 TZIDC 120 CI TZIDC 110 120 EN...