ABB TZIDC Service Instruction Download Page 2

TZIDC / EDP300

    |  SEI/POSITIONER/SUPPLY_AIR_FILTER-XA REV. A 

 

  

 

 

 

Replacing the supply air filters for the digital positioners TZIDC / EDP300 

 

  

Warnings 

 

The warnings in these instructions are structured as follows: 
 

 CAUTION 

The signal word ‘

CAUTION

’ indicates an imminent danger. 

Failure to observe this information may result in minor or 
moderate injury. 

 

Note 

Note

’ indicates useful or important information about the 

product. 

 

Replacing the filter element 

 

 

The digital positioner is equipped with a supply air filter that can 
collect small amounts of contaminants. 
The supply air filter prevents the digital positioner’s sensitive 
pneumatic components becoming clogged or damaged. 
 

Note 

The supply air filter is not a substitute for the required supply air 
treatment in accordance with DIN/ISO 8573-1. If the supply air is 
contaminated, the supply air filter can become clogged and 
must be replaced. 

 

1

  Filter insert 

2

  Screw plug 

 

 

Figure 1:  Supply air filter in the TZIDC 

 

 

 

 

1

  Filter insert 

2

  Screw plug 

3

  Filter element (sieve) in the supply 

air inflow (EDP300 only) 

Figure 2:  Supply air filter in the EDP300 

 

Replacing the filter insert 

 

 CAUTION 

Risk of injury from pressurized components 

The screw plug and the filter insert can be ejected if the screw 
plug is loosened when the pressurized air is switched on. 
•  Only ever loosen the screw plug when the positioner is 

depressurized and vented. 

 
1.  Disconnect the supply air to the positioner and vent the 

positioner. 

2.  Loosen the screw plug using a screwdriver. 
3.  Remove the contaminated filter insert using tweezers. 
4.  Replace the new filter insert as depicted in 

Figure 3

 or 

Figure 4

•  Ensure that the filter insert is aligned correctly. Ensure 

that the O-ring sits in the housing of the TZIDC correctly 
and is undamaged. 

5.  Hand-tighten the screw plug using a screwdriver. 
6.  For the EDP300, also check the filter element (sieve) in the 

supply air inflow for contamination and damage. 

7.  Power-up the supply air to the positioner and check all screw 

connections you loosened for tightness. 

 

Reviews: