Configuration
14
TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN
Warning!
Checks:
Write protection must be checked as follows:
1. TTH300-.H, TTF300-.H, and TTF350-.H locking via the LCD display with local keyboard
- Check whether the lock icon is displayed on the LCD display.
- Select the "Fault Signaling" menu and make sure the edit icon is not showing on the
LCD display.
- Press the Edit button and check that there is no response on the LCD display.
2. TTH200-.H, TTR200-.H, TTH300-.H, TTF300-.H, and TTF350-.H protection via DTM/EDD:
- LCD display and local keyboard available: Check as described under Point 1.
- No LCD display and local keyboard available (checking write protection):
Go to <Device>,<Parameterize> Current Output / Damping and change the damping
value, for example. Then select "Save Device Data in Device" and check whether the
message "Device is write-protected" is displayed.
Warning!
The software write protection does not lock again automatically. It remains unlocked until it is
specifically reset.
Diagnostics setup
The device's diagnostics setup meets safety requirements and includes the following error
detections:
• Sensor board communication error
• Sensor board error
• Sensor board A/D converter error
• Measuring error device temperature
• Sensor limit value alarm upper and lower
• TTH300-.H, TTF300-.H, and TTF350-.H, sensor error ch. 1. and ch. 2.
• Sensor configuration resistance thermometer, R in two-, three-, and four-wire circuit with
wire break and short circuit
• Sensor configuration thermocouple, mV with wire break
• Redundancy mode ch. 1 and ch. 2 with drift monitoring activated