SERVICING

 

SCOPE

 

Repair is  by  module  replacement.  Faulty  modules  are not  repairable in  the field.  They should be 
replaced by new modules and returned for repair. 

CAUTION 1

Before fitting a new module ensure that the setting of the configuration links  are  the  same  as 
that on the old module. 

CAUTION 2

This  module  contains  components  that  may  be  electrostatically  sensitive.  It  should  be 
transported and stored in its original packaging material. 

DIAGNOSIS

 

The TriBuild workstation is used for fault diagnosis.  In  the  case  of  an  Input/Output  fault  the 
Health LED on the faulty module will be extinguished. 

PREPARATION

 

To ascertain whether the chassis I/O slot containing the faulty module has been allocated a
hot repair partner, use one of the following methods: 

Check the system drawings 

Check the chassis wiring configuration 

Use the I/O chassis Configuration Report on the TriBuild workstation. 

Where  there  is  a hot  repair  partner  allocation,  use  the  ‘Dual-slot  hot  repair’  procedure, 
otherwise use the ‘Single-slot hot repair’ procedure. 

CONFIGURATION

 

Before fitting a new module ensure that 321/320 link setting is the same as that on the old 
module. 

REMOVAL AND REPLACEMENT

 

CAUTION 3

Failure to take the faulty module off-line before removing it from the chassis could trigger a fault 
alarm. 

CAUTION 4

Summary of Contents for Triguard SC300E

Page 1: ...state of all channels the circuit on line status and the health of the module The module which is compatible with dual slot hot repair can be fitted in any of the ten I O slots in the SC300E chassis...

Page 2: ...2 MDO16GNS October 2005 Issue 2 Triguard SC300E...

Page 3: ...6 Channel D O Module 48Vdc Mechanical coding block Upper ConfigurationLinks Link3 ICC B H L V HW GTZ Figure 1 1 General view and front panel detail 321 320 Link 1 Connector J1 Common Interface CI Modu...

Page 4: ...on in module 4W Module power consumption including field power dissipation in module 6W minimum load 36W maximum load Overall size mm Overall size inches 400 9U H x 397L x 28W 15 75H x 15 63L x 1 1W W...

Page 5: ...ber 2005 Issue 2 5 Triguard SC300E MDO16GNS 16 Channel D O Module 48Vdc TRANSPORT AND HANDLING The MDO16GNS must be transported and stored in its original packing material which should be retained for...

Page 6: ...y installed in a pattern determined by the module and corresponding set screws are removed from the chassis coder blocks to enable fitting Unused holes are plugged with set screws The chassis slot cod...

Page 7: ...t shown All the digital outputs are routed through connector J2 In the external connection diagram Figure 2 3 the following symbols are used 0 First mate long pin x Connector pin Earth Connected to ch...

Page 8: ...2 4 each path is controlled by its own microcontroller in the common interface In order to minimise the number of data connections across the 1kV system to field barrier the channel data are converted...

Page 9: ...n to switch its output alone to the opposite state and confirm the correct operation of its individual output switch The module power requirements are served from two different sources The power for t...

Page 10: ...10 MDO16GNS October 2005 Issue 2 Triguard SC300E D C Figure 2 4 MDO16GNS Block Diagram...

Page 11: ...cs on line off line status and signal status read write cycles to and from the SC300E processors via an I O communications bus All I O modules have an identification code which is read by the common i...

Page 12: ...12 MDO16GNS October 2005 Issue 2 Triguard SC300E Figure 2 5 Common interface Block diagram...

Page 13: ...s In the case of an Input Output fault the Health LED on the faulty module will be extinguished PREPARATION To ascertain whether the chassis I O slot containing the faulty module has been allocated a...

Page 14: ...Triguard SC300E When inserting a module ensure that it is aligned with the markings on the chassis rails and that it engages with the top and bottom guides Improper insertion may cause damage to the...

Page 15: ...EDs do not illuminate either the first or second time or fail to remain illuminated then the module must be considered faulty DUAL SLOT HOT REPAIR 1 Insert the new module into the vacant hot repair sl...

Page 16: ...16 MDO16GNS October 2005 Issue 2 Triguard SC300E SERVICE SUPPORT SPARES Spare parts and technical advice can be obtained from your local area offices...

Reviews: