ABB TDO16AIN Manual Download Page 9

TDO16AIN October 2005 – Issue 6

9

Triguard 

SC300E TDO16AIN 16-Channel D/O Termination Card 24Vdc

SUPPLEMENTARY INFORMATION

 

Dummy loads

 

Dummy  loads  are  only  to  be  connected  to  outputs  that  are  not  used. 

Do  not  connect  a

dummy load in parallel with a real output.

 

Digital output channel connections

 

Table 2-2 lists the digital output channel wiring connections and associated fuses for connector 
J1 and the screw terminals. 

Pin J1-1a is connected to the -ve bus (Figure 2-4 ). 

J1 pins, other than J1-1a and those listed in Table 2-2, are not connected. 

Screw Terminal

 

DIN41612 Connector J1

 

Channel

 

Digital 
output 
si g n al t o 
field 
device

 

Field loop 
return 
from field 
device

 

Field loop 
fused 
ac/dc 
supply to 
chassis

 

Digital 
output 
signal from 
chassis

 

Fuse

 

Link 
position 
for 
dummy 
load

 

1

1(+)

 

1(-)

 

J1-2a

 

J1-2c

 

F1

 

JP1-IN

 

2

2(+)

 

2(-)

 

J1-4a

 

J1-4c

 

F2

 

JP2-IN

 

3

3(+)

 

3(-)

 

J1-6a

 

J1-6c

 

F3

 

JP3-IN

 

4

4(+)

 

4(-)

 

J1-8a

 

J1-8c

 

F4

 

JP4-IN

 

5

5(+)

 

5(-)

 

J1-10a

 

J1-10c

 

F5

 

JP5-IN

 

6

6(+)

 

6(-)

 

J1-12a

 

J1-12c

 

F6

 

JP6-IN

 

7

7(+)

 

7(-)

 

J1-14a

 

J1-14c

 

F7

 

JP7-IN

 

8

8(+)

 

8(-)

 

J1-16a

 

J1-16c

 

F8

 

JP8-IN

 

9

9(L)

 

9(-)

 

J1-18a

 

J1-18c

 

F9

 

JP9-IN

 

10

 

10(L)

 

10(-)

 

J1-20a

 

J1-20c

 

F10

 

JP10-IN

 

11

 

11(L)

 

11(-)

 

J1-22a

 

J1-22c

 

F11

 

JP11-IN

 

12

 

12(L)

 

12(-)

 

J1-24a

 

J1-24c

 

F12

 

JP12-IN

 

13

 

13(L)

 

13(-)

 

J1-26a

 

J1-26c

 

F13

 

JP13-IN

 

14

 

14(+)

 

14(-)

 

J1-28a

 

J1-28c

 

F14

 

JP14-IN

 

15

 

15(+)

 

15(-)

 

J1-30a

 

J1-30c

 

F15

 

JP15-IN

 

16

 

16(+)

 

16(-)

 

J1-32a

 

J1-32c

 

F16

 

JP16-IN

 

Summary of Contents for TDO16AIN

Page 1: ...indication of fuse failure Overvoltage protection Dummy loads for unused digital output channels to prevent spurious operation of latent fault detection circuits in the associated digital output module Dummy loads are only to be connected to outputs which are not used This document is intended to provide a general understanding of the function of the TDO16AIN sufficient to enable basic maintenance...

Page 2: ...onnectors do not exceed 16A total Fuse in each positive line to field 1A fast acting indicating Chassis cable connector 34 way DIN41612 Field cable connector Screw terminal to suit 2 5mm2 wire 16 AWG Fuse blown indication Local Fuse blown LED one per card Remote Fuse blown alarm output PL1 can be connected to Fuse blown LED on Power Distribution Panel PDD24 Safety ground terminal TS1 M3 threaded b...

Page 3: ...emperature operating 5 C to 60 C Temperature storage 25 C to 70 C Humidity 5 to 95 non condensing at ambient 40 C EMC RFI Immunity Tested and certified to IEC 1131 Part 2 1994 Vibration Shock Tested and certified to IEC 1131 Part 2 1994 Certification General Certification Ref SC300E TMR Product Guide ref 008 5209 TRANSPORT AND HANDLING The termination card must be transported and stored in its ori...

Page 4: ... that can be snapped onto all commercially available styles of DIN EN mounting rail Connection to the chassis backplane is via a multicore cable terminated at either end by a DIN41612 connector Figure 2 2 shows the TDO16AIN with the DIN41612 connector attached and mounted on rail EN 50022 type NS 35 5 Figure 2 1 General view and component layout ...

Page 5: ...TDO16AIN October 2005 Issue 6 5 Triguard SC300E TDO16AIN 16 Channel D O Termination Card 24Vdc Figure 2 2 Leading dimensions and mounting schematic ...

Page 6: ...NS Table 2 1 Fixed terminal Details Field terminals 1 to 16 Screw terminal to suit 2 5mm2 wire Chassis connector J1 Connector 34 way DIN41612 female Field power supply inputs FS1 to FS4 Header 2 way Molex Minifit Jr Alarm output PL1 Header 2 way Molex KK Ground terminal TS1 Provision for M3 ring terminal ...

Page 7: ...one of the four inputs FS1 to FS4 For high load applications or where the channel groups require different supply voltages cut the links and supply FS1 to FS4 individually Each digital output channel is powered from a common ve bus An indicating fuse is fitted in the digital output signal line to the field device The fuse failed output from each fuse is connected to a common alarm bus If any fuse ...

Page 8: ...ndication is taken from the chassis module digital output signal An alarm will be signalled only when the fuse has failed and this output is high Power distribution panel PDD24 has a Fuse blown alarm indicator with provision for multiple inputs This facility can be wired to provide fuse blown indication for an entire cabinet ...

Page 9: ...ew Terminal DIN41612 Connector J1 Channel Digital output signal to field device Field loop return from field device Field loop fused ac dc supply to chassis Digital output signal from chassis Fuse Link position for dummy load 1 1 1 J1 2a J1 2c F1 JP1 IN 2 2 2 J1 4a J1 4c F2 JP2 IN 3 3 3 J1 6a J1 6c F3 JP3 IN 4 4 4 J1 8a J1 8c F4 JP4 IN 5 5 5 J1 10a J1 10c F5 JP5 IN 6 6 6 J1 12a J1 12c F6 JP6 IN 7 ...

Page 10: ...TION Before replacing a blown fuse ascertain the cause of failure and take the appropriate remedial action CONFIGURATION Links LK1 to LK4 are connected by default see Figure 2 3 If all the links are cut power supply connectors FS1 to FS4 will feed individual digital output channel groups as follows Table 3 1 Power supply connectors Link no Channels FS1 Channels 1 to 4 FS2 Channels 5 to 8 FS3 Chann...

Page 11: ...d SC300E TDO16AIN 16 Channel D O Termination Card 24Vdc SERVICE SUPPORT SPARE PARTS Spare parts and technical advice can be obtained from your local area offices LIST OF SPARES Circuit Ref Part No Details F1 to F16 380 0013 1A Indicating fuse ...

Reviews: