![ABB T 900 DU V1000 Operation Instructions Manual Download Page 31](http://html1.mh-extra.com/html/abb/t-900-du-v1000/t-900-du-v1000_operation-instructions-manual_4073492031.webp)
31
ABB STOTZ-KONTAKT
2CDC 106 011 M5701
D
Auslösekennlinien
E
Tripping characteristics
F
Courbes de déclenchement
S
Utlösningskurvor
I
Caratteristiche di intervento
SP
Curvas características
de disparo
RUS
Характеристики
срабатывания
three
pole
4)
Fuse 500A NH
5)
two pole
3)
265.0 ... 375.0 A
two pole
3)
10.6 s
3.7 s
3.0 s
Tripping time
2)
Multiples of rated
current
1)
3 x Ie
6 x Ie
7.2 x Ie
three pole
4)
16.0 s
5.3 s
4.3 s
Multiples of rated current
1)
Tripping time
2)
three
pole
4)
Fuse 800A NH
5)
two pole
3)
355.0 ... 500.0 A
two pole
3)
12.0 s
4.5 s
3.6 s
Tripping time
2)
Multiples of rated
current
1)
3 x Ie
6 x Ie
7.2 x Ie
three pole
4)
17.0 s
6.0 s
4.8 s
Multiples of rated current
1)
Tripping time
2)
1)
2)
3)
4)
5)
Vielfaches vom Nennstrom
Auslösezeit
2-polig
3-polig
Sicherung
Multiple du courant de reglage
Temps de déclenchement
2 broches
3 broches
Fusible
Multipelfaktor för utlösningsström
Utlösningstid
2-polig
3-polig
Säkring
Multiplo della corrente di regolazione
Tempo di apertura
Bipolare
Tripolare
Fusibile
Múltiplos de la intensidad aplicada
tiempo de disparo
de 2 polos
de 3 polos
Fusible
Êîýôôèöèåíò òîêà óñòàâêè
Âðåìÿ ñðàáàòûâàíèÿ
Äâóõïîëþñíûé
Òðåõïîëþñíûé
Ïðåäîõðàíèòåëü
D
F
S
I
SP
RUS
Summary of Contents for T 900 DU V1000
Page 2: ...2 ABB STOTZ KONTAKT 2CDC 106 011 M5701 ...