XM/SM/XE MAGNETIC FLOWMETER
CALIBRATION
I - 5
CALIBRATION
This section details the calibration functions of the STT04 terminal
while interfacing an XM/SM/XE Mag Flow Meter. There are two types
of calibration functions:
•
Empty pipe detector.
•
D-to-A adjust.
NOTES:
1.
When calibrating, a field device must be connected to the
STT04 terminal.
2.
To change calibration or configuration parameters of a field
device that is connected to an IMFBS01 module, the transmitter
must be taken off-line. This is done at the INFI 90 OPEN console.
Refer to Figure
for an overview of the calibration functions.
Make a selection using the arrow keys.
Make a selection using the arrow keys.
Specify values using the number keys. The
UNITS
displayed will be those designated in a previous
screen. After entering a value press
.
Make a selection using the arrow keys.
Key
Display
Comments
E N T E R
FLOW DIRECTION:
→
FWD AND REV
FWD ONLY
E N T E R
EMPTY PIPE DET.:
→
OFF
ON
E N T E R
UPPER PV ALARM
nnn.nn UNITS
LOWER PV ALARM
nnn.nn UNITS
ENTER
E N T E R
STORE THIS
CONFIGURATION?
NO
→
YES
E N T E R
ID TAGNAME
READY