—
ABB Australia Pty Limited
For enquiries
ABB contact centre: 1800 60 20 20
E-mail: [email protected]
www.stanilite.com.au
© Copyright 2020 ABB. All rights reserved.
Troubleshooting guide
If you have installed and connected the fitting as per the instructions listed earlier and it does
not function correctly, use the following table as a guide to fixing the problem. Look up the
type of fault in the left column and check the possible causes from the right column.
If the fitting still does not work after checking these possible causes, contact ABB customer
service in Australia on 1800 60 20 20.
No. Fault
Possible causes
1
LED not lit;
or
LED not flashing green
AC supply not connected;
or
AC supply turned off
2
LED is flashing green but AC lamp does not come on
when connected to mains
Switch active supply turned off;
or
Missing loop from unswitched to switched active;
or
Lamp damaged;
or
Lamp not inserted properly
3
LED is flashing green but lamp does not come on when
test switch is pressed
Lamp damaged or lamp not inserted properly;
or
Battery pack not connected;
or
Battery pack damaged;
or
Test switch damaged
4
LED not red after the commissioning
Battery pack not connected;
or
LED wire not properly inserted into the terminal
block
5
Lamp is lit momentarily when test switch is pressed;
or
When mains fail
Battery not fully charged (allow up to 24 hours);
or
Battery pack damaged
6
LED is constant green
Fitting self checks fail - return to manufacturer
7
Fitting LED is not flashing yellow/orange under wink
node command
Fitting is not receiving communication signal. Check
data cable wiring path and cable connections. Refer
to Nexus RF user guide.
Construction sites
Continuously switching off the mains power
supply that is connected to emergency light
fittings during the construction phase of an
installation will cause these fittings to discharge
and charge their batteries many times over a
short period; this can shorten life of the battery.
ABB does not recommend such practices and
may not honour the warranty on batteries when
they are subjected to such harsh operating
conditions. Emergency light fittings are designed
to be discharge tested once every 6 months as
per AS/NZS 2293.2, subjecting the product to
repeated discharge or charge cycles is regarded
as an abuse of the fittings.
Testing precautions
Once the fitting is permanently connected to the
mains supply, a commissioning discharge test as
required in AS/NZS 2293.2 must be carried out.
You will need to allow 24 hours for the battery to
fully charge prior to conducting this test,
presently (at the time of writing), the standard
requires that fittings operate in emergency mode
for a period not less than 2 hours for their
commissioning test and for not less than 90
minutes thereafter (it is required that 6 monthly
discharge tests be carried out). You will need to
keep the records for the commissioning test and
enter them into the building emergency services
logbook or via other recording methods as
allowed by AS/NZS 2293.2.
—
I N S TA LL ATI O N M A N UA L
Stanilite®
Power pack T8
Nexus® RF
Thank you for choosing ABB product
Please read this document thoroughly before
commencing installation and retain for future
reference. Contact ABB customer service in
Australia on 1800 60 20 20 if you need any
assistance. The installation instructions were
correct at the time of print. To reflect changes in
technology and Australian standards; ABB
reserves the right to amend the instructions
without notice. Updated document can be found
on the Stanilite website.
Safety warning
In Australia and New Zealand, only licensed
electricians are permitted by law to work with
240 volt electrical installations.
Do not attempt to install or connect this product
unless you are a licensed electrician.
Turn off and isolate the electrical supply before
connecting this fitting to the building wires.
Do not touch the terminals of the terminal block
when the light fitting is energised.
The only user-serviceable part is the battery.
Do not attempt to service other parts of the
fitting as this will void the warranty.
As the installer, it is your responsibility to ensure
compliance with all relevant building and safety
codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to
the applicable standards for data and mains
cabling installation procedures and
requirements.
This document covers
What’s inside the box
Safety warning
Power pack T8 Nexus RF
Installation instructions
Installation manual
Removal instructions
Warranty information
Testing precautions
Troubleshooting guide
Important to note:
• This product is designed for indoor use only.
EMC warning
Power pack complies with EMC regulations. We
advise that if you incorporate this pack into
your product (batten/fitting) you must test the
complete (product/fitting) for EMC compliance.
PL Lamp warning
For PL lamp application it is recommended that
the power pack be used without a LDR. The fitting
should be designated as a non-maintained fitting.
The LDR is not designed to be affixed to a PL lamp.
If AC lamp monitoring is required then the LDR
must be mounted adjacent to the PL lamp. Please
contact ABB customer service on 1800 60 20 20
if you require more information. Specific PL lamp
power packs are supplied without a LDR and are
programmed as non-maintained.
Nexus RF (wireless system)
The Nexus RF power pack is a wireless RF system
monitor conversion kit suitable for AC fluorescent
luminaire to be converted to Nexus RF fluorescent
emergency luminaire, they communicate via a
proprietary RF network system. The power pack
comes complete with Nexus RF MAC address
label. Affix the Nexus RF MAC address label
supplied with the power pack on to the retrofitted
emergency fitting in a recognisable position for
recording upon installation
Doc no. 29-01092_1
9
A
K
K
10
76
8
0
A
8
4
24
-
A
-
Ju
n
e
20
20