Troubleshooting guide
If you have installed and connected the fitting as per the instructions and it does not function
correctly, use the following table as a guide to fixing the problem. Look up the type of fault in
the left column and check the possible causes from the right column.
If the fitting still does not work after checking these possible causes, please contact your place
of purchase.
No. Fault
Possible causes
1
LED light source and red LED not lit
AC supply not connected;
or
AC supply turned off;
or
Test switch damaged
2
LED light source is lit but red LED not lit
AC supply not connected;
or
AC supply turned off;
or
Test switch damaged;
or
Battery not connected or faulty
3
LED light source does not switch to emergency mode
when the test button is pressed
Test switch damaged;
or
Battery not connected or faulty
4
LED light source works momentarily on emergency
when the test button is pressed
Battery not yet charged (allow up to 24 hours)
Thank you for choosing ABB product
Please read this document thoroughly before
commencing installation and retain for future
reference. The installation instructions were
correct at the time of print. To reflect changes in
technology and Australian standards; ABB reserves
the right to amend the instructions without notice.
Updated document can be found on the Stanilite
website.
Safety warning
In Australia and New Zealand, only licensed
electricians are permitted by law to work with 240
volt electrical installations. Do not attempt to
install or connect this product unless you are a
licensed electrician. Turn off and isolate the
electrical supply before connecting this fitting to
the building wires. Do not touch the terminals of
the terminal block when the light fitting is
energized. The only user serviceable part is the
battery pack. The LED light source is not user
serviceable. Do not attempt to service other parts
of the fitting as this will void the warranty. As the
installer, it is your responsibility to ensure
compliance with all relevant building and safety
codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to
the applicable standards for mains cabling
installation procedures and requirements.
This document covers
What’s inside the box
Safety warning
Ecoexitblade Base assembly
Testing precautions
Ecoexitblade Blade assembly
Troubleshooting guide
Pictograph insert pack
Instructions on
Installation manual
Installation
Warranty information
Battery replacement
Product removal
In accordance with AS 60598.2.2:2016 the
luminaire classification is CA90. Insulation can
abut but cannot cover the luminaire.
Where possible we recommend to leave a gap
surrounding the luminaire.
Not suitable for use with loose-fill insulation.
No fire rated box is required for the product.
Class II luminaire, protection against electric
shock is provided by double insulation or
reinforced insulation.
This luminaire is suitable for indoor use only.
Product Specification
• Norminal design Voltage: 240 V~50 Hz.
• Line current: 43 mA
• In-rush current: 38.5 A/50
μs
•
Circuit power: 2.9 W standby, 4.4 W max.
•
Battery: LiFePO4 3.2 V 1500 mAh
•
Viewing Distance (m): 24
•
Classification (C0/C90): D10 / C10
•
Test Mode: Manual
•
Protection Class: II
•
IP Rating: IP20
•
Operating Temp. (
℃
): 10 to 40
90