17
Fig. 10. Voltage regulators SPAU 341 C1 in parallel operation using the minimizing circulating
current principle. The operation mode of the regulators is automatically selected according to the
circuit breaker configuration. The communication between the regulators is achieved by using
SPA/LON gateways.
Table 3. Regulator mode compared to circuit breaker configuration
CB 1
CB 2
CB 3
Regulator 1
Regulator 2
open
closed
open
manual
manual
closed
closed
open
automatic
manual
open
closed
closed
manual
automatic
closed
closed
closed
parallel
parallel
open
open
closed
manual
automatic
closed
open
open
automatic
manual
closed
open
closed
automatic
automatic
M
Raise
Lower
Man'
Auto'
CB1
CB2
T1
SPAU 341 C
R1 Adr. 10/11
L
N
Parallel
(RSV)
–
SP
A-ZC 100
AB
Serial
port
–
–
Single/
Parallel
Man' Auto'
M
Raise
Lower
Man'
Auto'
CB3
T2
SPAU 341 C
R2 Adr. 20/21
L
N
Parallel
(RSV)
–
SP
A-ZC 100
AC
Serial
port
–
–
Single/
Parallel
Man' Auto'
Tx
Rx
Tx
Rx
U12
IL1
U12
IL1