10
Configuration
switches
Part of the starting and tripping signals from
the relay modules are permanently connected
to the output relays, whereas part of the output
signals are routed through switchgroup SGR.
The switchgroup is located at the front edge of
the output relay module. The switches are set
through the opening in the relay system front
panel.
The switchgroups SGB on the PC-boards of the
relay modules SPCU 1C6 and SPCU 3C15 are
used for routing incoming external blocking sig-
nals to the protection stages to be blocked.
The functions of the switchgroups SGB and
SGR are described in the tables as follows:
Switchgroup SGR on relay system panel
Switch
Function
Factory
setting
SGR/1 Tripping signal from stage U< to output relay A
1
SGR/2 Tripping signal from stage 3U<< to output relay A
1
SGR/3 Tripping signal from stage U
0
> to output relay A
1
SGR/4 Tripping signal from stage U
0
>> to output relay A
1
SGR/5 Tripping signal from stage U< to output relay B
1
SGR/6 Tripping signal from stage 3U<< to output relay B
1
SGR/7 Starting signal from stage U< to output relay C
1
SGR/8 Starting signal from stage 3U<< to output relay D
1
Switchgroup SGB on PC-board in residual overvoltage relay module SPCU 1C6
Switch
Function
Factory
setting
SGB/1 Not in use
0
SGB/2 Not in use
0
SGB/3 Not in use
0
SGB/4 Blocking signal BS1 for blocking of U
0
>-tripping
0
SGB/5 Blocking signal BS1 for blocking of U
0
>>-tripping
0
SGB/6 Not in use
0
SGB/7 Not in use
0
SGB/8 Not in use
0
Switchgroup SGB on PC-board in undervoltage relay module SPCU 3C15
Switch
Function
Factory
setting
SGB/1 Not in use
0
SGB/2 Not in use
0
SGB/3 Not in use
0
SGB/4 Blocking signal BS1 for blocking of U<-tripping
0
SGB/5 Blocking signal BS1 for blocking of 3U<<-tripping
0
SGB/6 Not in use
0
SGB/7 Not in use
0
SGB/8 Not in use
0