10
Technical data
Low-set stage I
0
>
Start current
0.2…2% x I
n
,
1…10% x I
n
or
5…50% x I
n
Start time, typically
75 ms
Operate time t>, definite time
0.05...1.00 s or
0.5...10.0 s
Reset time, typically
70 ms
Reset ratio, typically
0.96
Operate time accuracy
±
2% of set value or
±
40 ms
Operation accuracy
- within the setting range 0.2…2% x I
n
±
5% of set value
- within the setting range 2…50% x I
n
±
3% of set value
High-set stage I
0
>>
Start current
1…8% x I
n
&
∞
,infinite or
5…40% x I
n
&
∞
, infinite or
25…200% x I
n
&
∞
, infinite
Start time, typically
60 ms
Operate time t>>
0.05...1.00 s or
0.5...10.0 s
Reset time, typically
70 ms
Reset ratio, typically
0.96
Operate time accuracy
±
2% of set value or
±
40 ms
Operation accuracy
±
3% of set value