7. GOOSE control blocks
8. GOOSE inputs
6.4.1.
Adding Device object
To build the object tree:
1. Add an IEC 61850 Device object in the communication structure by
selecting the project name.
In the example the project Protocol Test is selected.
2. Right-click Protocol Test
3. Select
New > IEC 61850 > SPA-ZC 40x
, see Fig. 6.4.1.-1.
A project can contain several IEC 61850 Device objects, for example all
substation feeder configurations and exported communication must be done
separately for each device.
A040023B
Fig. 6.4.1.-1
Adding an IEC 61850 Device object
Ensure that the new IED name is unique within the planned network by
renaming the IED, for example REF545_F1.
A Tunneling Device object cannot be configured for an IEC
61850 gateway.
6.4.2.
Adding Logical Device objects
Communication Engineering Tool (CET) creates logical device LD0
automatically for SPA-ZC400 when creating a new IED. All datasets and
reporting control blocks (RCB) are grouped under LD0 for event handling. It
has also basic logical nodes and data objects for diagnostics and device
information.
1MRS755347
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
SPA-ZC 400
Summary of Contents for SPA-ZC 400
Page 1: ...Ethernet Adapter SPA ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual ...
Page 2: ......
Page 8: ...8 ...
Page 12: ...12 ...
Page 14: ...14 ...
Page 22: ...22 ...
Page 30: ...30 ...
Page 60: ...60 ...
Page 72: ...72 ...
Page 74: ...74 ...
Page 112: ...112 ...
Page 114: ...114 ...
Page 116: ...116 ...
Page 118: ...118 ...
Page 120: ......
Page 121: ......