background image

Electromagnetic compatibility tests

EMC immunity test level meets the requirements listed below
1 MHz burst disturbance test, class III

Common mode

 

Differential mode

According to the IEC 60255-22-1
2.5 kV

 

1.0 kV

Electrostatic discharge test, class IV

 

For contact discharge

 

For air discharge

According to the IEC 6100-4-2 and 

 

IEC 60255-22-2
6 kV

 

8 kV

Radio frequency interference tests

Conducted, common mode

 

 

Radiated, amplitude-modulated

 

 

Radiated, pulse-modulated

According to the IEC 61000-4-6 and
IEC 60255-22-6

10 V (rms), f = 150 kHz ... 80 MHz

According to the IEC 61000-4-3 and
IEC 60255-22-3

10 V/m (rms), f = 80 ... 2700 MHz

According to the ENV 50204 and
IEC 60255-22-3

10 V/m, f = 900 MHz

Fast transient disturbance tests

 

All terminals

According to the IEC 60255-22-4 and

 

IEC 61000-4-4

4 kV

Surge immunity test

Power supply

According to the IEC 60255-22-5 and IEC 61000-4-5

4 kV, line-to-earth

 

2 kV, line-to-line

Power frequency (50 Hz) magnetic field 

According to the IEC 61000-4-8

300 A/m continuous

Electromagnetic emission tests

Conducted, RF-emission (Mains term.)

Radiated RF-emission

According to the EN 55011

EN 55011, class A, IEC 60255-25

EN 55011, class A, IEC 60255-25

CE compliance

Complies with the EMC directive 2004/108/EC and the LV 
directive 2006/95/EC

Standard tests

Mechanical tests
Vibration tests (sinusoidal)
Shock and bumb test

According to the IEC 60255-21-1, class I
According to the IEC 60255-21-2, class I

 

Supply current consumption

Running 

340 mA

Start up

430 mA

 

Ethernet Adapter

SPA-ZC 400

1MRS755450

Technical data (cont´d)

6

RoHS Compliance

Complies with the RoHS directive 2002/95/EC

Reviews: