abb
SafeLink
SF
6
Insulated Ring Main Unit
Installation and Operating Instructions
SLMIO ver 2.12
ABB Ltd, Switchgear Division, Auckland, New Zealand
2
Filling Pressure @ 20°C:
1.2bar abs
Quantity:
1kg approximately
Minimum Operating Pressure:
1.1bar abs
1.1.2 Electrical
Data
General Ratings @ 1.1bar abs SF
6
Pressure
Rated Voltage:
12kV
Lightning impulse Voltage:
95/110kV BIL
Withstand Voltage:
28/32kV for 1 minute
Frequency:
50Hz
Rated Current:
400A or 630A
Withstand Current:
16kA rms or 20kA rms
Withstand Current Duration:
3sec
Recommended Maximum
Cable Size:
300mm² 3-core cable
500mm² single-core cable
Load Break Switch
(E3, M2 rating to IEC 60265-1:1998)
Rated Current:
400A or 630A
Short Circuit Making Current:
40kA peak or 50kA peak
Switch-Fuse
Rated Current:
200A
Prospective Fault Withstand:
20kA rms
Max Transformer size:
1000kVA
Bushings
Series 400 (DIN 47632) with adapted in-line bolted connection
Rated Current:
630A
Fuses
DIN 43625
Max 100A ABB Type CEF 12kV or equivalent
Length:
292mm
Diameter:
87mm
Refer to Section 2.4 on page 10 for the fuse selection chart.