1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 131
40 - Ekip Com Modbus RTU
Ekip Com Modbus RTU
is a communication accessory that enables Ekip Touch to be integrated
into a RS-485 network with Modbus RTU communication protocol, with remote supervision and
control functions, in two different modes, master and slave.
From remote it is possible to:
read information and Ekip Touch measurements
manage certain commands, including opening and closing actuator (MOE-E)
access to information and parameters that are not available on the display
if connected to a withdrawable circuit-breaker, check the status of inserted / extracted
NOTE: the remote open and close commands to the switch can be run only if Ekip
Touch is in Remote configuration
To map the module in its own communication network, the document System Interface is
available (page 128), in which all the necessary communication and command details are listed.
To connect
Ekip Modbus RTU
to Ekip Touch, the
Ekip Cartridge
(page 129) and
Ekip Supply
(page 130) accessories are required.
Models
Ekip Touch can be configured with two different modules that are compatible with the Modbus
RTU protocol:
Ekip Com Modbus RTU
and
Ekip Com Modbus RTU Redundant
.
The two modules are identical in terms of characteristics and installation methods, except for:
display menus on unit, cablings and addresses for external communication, that are specific for
each model.
NOTE: if not specified, the information in the following chapter applies to both models
Both modules can be connected simultaneously to Ekip Touch to increase the potential of unit
(for example: for applications in which great network reliability is necessary).
IMPORTANT: in each Ekip Touch can be installed only one module per type; it is
not admitted the connection of two equal modules (for example: two Ekip Com
Modbus RTU Redundant)
Connections
Consult:
the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
The connections must be made with Belden 3105A or equivalent cables.
the instruction sheets 1SDH002009A1503 to connect the module to
Ekip Supply
and
Ekip Touch.
Supply
Ekip Com Modbus RTU
is supplied directly by the
Ekip Supply
module to which it is connected.
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...