background image

1SDH002031A1002    ECN000092998    Rev. B 

SACE Tmax XT2 

– XT4 | 129 

38 -  Ekip Cartridge 

 

 

 

Ekip Cartridge

 is an external accessory that can be installed on a standard 35 mm DIN rail (DIN 

EN 50022 type TS 35x15 mm), which allows other external accessories to connect to Ekip Touch: 

 

All cartridge modules (e.g. 

Ekip Supply

Ekip Com

, etc) 

 

engaged/disengaged signal contact, in case of a CB in a detachable configuration 

 
 

Models 

 

Two different models are available that allow two or four modules to be connected respectively. 

 

 

IMPORTANT: one module must always be Ekip Supply  
 
 

 

Connections 

 

Ekip Cartridge

 has two terminal blocks: 

 

 

Figure 30 

 

Connector 

Description 

Terminal for connecting the engaged/disengaged status contact 

 

 

NOTE: by default Ekip Cartridge is supplied with a jumper on the terminal 
block 
 

To  use  the  engaged/disengaged  status  signal,  remove  the  jumper  from  the 
connector and connect the cables coming from the fixed part of the CB 

Terminal for the connection of 

Ekip Cartridge

 to Ekip Touch: 

 

Pin 

Description 

K2 

Power output for Ekip Touch (+24V DC) 

K1 

Power output for Ekip Touch (-24V DC) 

W3 

CAN bus 

W4 

CAN bus 

 

 
Access to all external connections are available on the respective modules, on the top side of 

Ekip Cartridge

 
 

Assembly 

 

To connect the module to Ekip Touch see the instruction sheets 1SDH002009A1503. 
 
 

 

 

Summary of Contents for SACE Tmax XT2

Page 1: ...H002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 User manual for use and maintenance of Ekip Touch Trip units for Tmax XT2 XT4 low voltage molded case circuit breakers Power and productivity for a better worldTM ...

Page 2: ...100 28 Class 1 Power Energy Metering 103 29 Datalogger 104 30 Network Analyzer 106 SETTINGS 113 31 Main settings 113 32 Supplemental settings 117 TEST 119 33 Test 119 ADDITIONAL FUNCTIONS 121 34 Power Controller 121 35 Load Shedding 122 36 Interface Protections IPS 124 EXTERNAL ACCESSORIES 127 37 Introduction and System interface 127 38 Ekip Cartridge 129 39 Ekip Supply 130 40 Ekip Com Modbus RTU ...

Page 3: ... TRIP Ekip Touch Trip unit for CB SACE Tmax XT2 XT4 equipped with LCD display available in four different versions Trip coil CB opening actuator controlled directly by the Trip unit TRIP Final phase of a timing protection or of a test command that except for particular configurations provided by the trip unit coincides with the activation of the trip coil which instantly opens the bars of each pol...

Page 4: ...ity can create IMPORTANT This manual details the operations that can be performed by people trained in the electrical field All the remaining operations described in the manual must be carried out by experts in the electrical field ABB will not be held responsible for damage to property or persons due to non compliance with the instructions contained in this document Requirements and supporting do...

Page 5: ...ts that can be connected to communication networks the buyer installer or end customer is responsible for ensuring security measures necessary to prevent risks deriving from connection to communication networks are followed These risks include among others the use of the product by unauthorized personnel changes to its normal operation access to and modification of information The buyer installer ...

Page 6: ...antities including currents voltages powers energies 2 Protection based on the measurements detected and the parameters configured by the user the Trip unit checks for an alarm and if necessary commands the tripping of the circuit breaker 3 Signaling management of contacts and communication networks to optimize system efficiency communication between different CBs and other functionalities The Eki...

Page 7: ...vailable in two versions Ekip Touch LSI and Ekip Touch LSIG Both versions have default functions and can be configured with various additional software packages extensions Default Function Page Standard Protections 35 Standard Sizes 96 Additional SW packages Function Page Measuring 100 Voltage Protections 1 46 Advanced Voltage Protections 1 50 Frequency Protections 1 54 Power Protections 1 57 ROCO...

Page 8: ...can be configured with various additional software packages extensions Default Function Page Standard Protections 35 Standard Sizes 96 Measuring 100 Additional SW packages Function Page Voltage Protections 46 Advanced Voltage Protections 50 Frequency Protections 54 Power Protections 57 ROCOF Protections 64 Adaptive Protections 65 Class 1 Power Energy Metering NOTE 103 NOTE package available only w...

Page 9: ... Page Standard Protections 35 Standard Sizes 96 Measuring 100 Voltage Protections 46 Frequency Protections 54 Power Protections NOTE 57 Adaptive Protections 65 Class 1 Power Energy Metering 103 Datalogger 104 Network Analyzer 106 Additional SW packages Function Page Advanced Voltage Protections 50 Power Protections NOTE 57 ROCOF Protections 64 NOTE By default Ekip Hi Touch has some protections fro...

Page 10: ...oltage Protections 46 Frequency Protections 54 Power Protections 1 57 Adaptive Protections 65 Motor Protections 66 Additional SW packages Function Page Advanced Voltage Protections 50 Power Protections 1 57 ROCOF Protections 64 Class 1 Power Energy Metering 2 103 Datalogger 104 Network Analyzer 106 NOTES 1 By default Ekip M Touch has some protections from the complete package the remaining protect...

Page 11: ...rnal module Other external modules and accessories available with direct connection to the internal terminal board or to the rear connectors are Name Function Page Ekip Signalling 10K Signaling with input output 203 Ekip Multimeter Display from the front of the panel 204 External neutral Neutral protection with CB 3P 204 Supervision configuration and reporting functions are also guaranteed with ad...

Page 12: ...he following tools DOC to design single circuit diagrams of low and medium voltage electrical systems choose the switching and protection devices and verify and coordinate the protections CAT for technical commercial estimates of ABB products Curves to draw calibrate and print the tripping curves of protection devices OTC to verify the thermal behavior of panels and to size the fans and air condit...

Page 13: ...kip Touch can also be powered directly by the internal power sensors Parameter Operation limits Minimum three phase power on startup 0 2 In Auxiliary power supply Ekip Touch can be connected to an external auxiliary power source useful for enabling some functions such as communication on the Local Bus recording of manual operations some measurements and the data logger The auxiliary power supply c...

Page 14: ...of Startup and Maintenance and malfunctions for Ekip Touch For other operations see the Installation Instructions and the Technical Catalog see page 4 for references 7 Startup General checks Before startup it is necessary to perform the following checks Points to inspect Checks Main connections Ground connections If present connection and tightness of the external Neutral voltage V0 If included co...

Page 15: ...menu and the absence of alarms External Neutral sensor 1 Check the connection of the sensor to the rear terminal block 2 Power up the Trip unit and check turning on 3 Check on Settings Circuit breaker menu that Configuration 3P N otherwise change the parameter 4 Check absence of alarms Zone selectivity 1 Check the selectivity connections between Ekip Touch and the other units as per the wiring dia...

Page 16: ...ening test from the Test CB Test menu with the Open CB command and make sure that the CB has opened 5 Repeat the test from the Test CBTest menu with the Close CB command and make sure that the CB has closed AUP circuit breaker status inputs for the removable version of the CB 1 Check that the status of the removable circuit breaker is correctly read by the Trip unit using the Information Circuit B...

Page 17: ...he following checks 1 Make sure Ekip Touch is clean removing dust and any traces of other materials using dry clean rags if necessary use mild detergents for excessive dirt a laminate thinner like Henkel 273471 or Chemma 18 or equivalent can be used 2 Make sure that there are no foreign objects near connectors or terminals Check Ekip Touch Perform the checks listed in the chapter Startup on page 1...

Page 18: ... cable missing on one or more Ekip Com modules equipped with Ethernet connection Internal error Internal error For this type of error contact ABB Invalid date Incorrect date and time set in the menus Settings System Date and Settings System Time IEEE1588 synch Synchronization problem of the IEEE 1588 synchronization module Local Bus Unit turned on with auxiliary power supply Local Bus parameter en...

Page 19: ...ssible causes and suggestions for resolving them NOTE Check the error messages on the display before consulting the table if the suggestions provided do not resolve the problem contact ABB customer support if possible providing the alert produced by the Ekip Connect software Malfunction Possible causes Suggestions Communication problems with terminal modules Circuit breaker in extracted position V...

Page 20: ...rmed The Trip coil is not connected correctly Check the Trip coil connection and the messages on the display The CB alert has not been reset Press the reset button The bus power is greater than zero Proper operating condition The expected trip did not occur Trip disabled Proper operating condition enable trip if necessary Reaction times different from expectations Wrong threshold time curve select...

Page 21: ...et parameters related to connected accessory modules Run tests Components The Ekip Touch interface includes an LCD display buttons for quick access and menu navigation status LEDs and a service connector for some external accessories Figure 8 Pos Description A LCD Display B iTEST button C Right Up button D ESC button E Left Down button F Enter button G Power LED H Warning LED I Alarm LED J Service...

Page 22: ... Touch Power LEDs and the modules will flash together More details in the chapter of additional functions from Ekip Connect page 118 Warning Yellow Signals the presence of some alarms Off no alarm On fixed pre alarm of an enabled protection or error in the status contacts Alarm Red Signals the presence of an alarm Off no alarm On fixed trip signal On flashing timing protection active or alarm for ...

Page 23: ...ating through the submenus Enter Press to Display the main menu when the Trip unit shows the measurement pages Select the desired submenu Confirm the entry of the password required to update the Trip unit s parameters Confirm or cancel the changes to the Trip unit s parameters Right Up Press to Scroll through the various measurement pages Move to the right while navigating the main menu Move up du...

Page 24: ... possible to view more measurement pages Figure 10 The list of additional available measurement pages depends on the presence or absence of Neutral voltage always present in the case of a tetrapolar Trip unit to be configured in case of a 3P N Trip Unit If the Trip Unit is configured without Neutral voltage the following additional pages are available Maximum measurements page maximum phase power ...

Page 25: ...l time total phase power measurements Energy measurements page total active reactive and apparent energy measurements Power Controller measurements page if the specific package is present see page 121 for details Load Shedding measurements page if the specific package is present see page 123 for details Diagnosis bar and Alarm list The Diagnostic Bar shows the malfunctions detected by the unit sho...

Page 26: ...d Other possible values black text on a white background Figure 14 Protections Menu In the Protections menu it is possible to configure the following protections 1 Name Parameters SW package Page L List and description in the dedicated chapter Standard Protections 36 S List and description in the dedicated chapter 38 S2 List and description in the dedicated chapter 38 I List and description in the...

Page 27: ...COF Protections 64 R STALL 2 List in the dedicated chapter Motor Protections 67 R JAM 2 List in the dedicated chapter 67 UC 2 List in the dedicated chapter 68 U 2 List in the dedicated chapter 68 PTC 2 List in the dedicated chapter 69 V DIR VINV 2 List in the dedicated chapter Interface Protections IPS 124 59 S1 2 List in the dedicated chapter 124 Synchrocheck List in the dedicated chapter NOTE 3 ...

Page 28: ... in the dedicated chapter 102 Harmonic distor Control to enable harmonic distortion of the powers 44 Ekip Synchrocheck 2 Description in the dedicated chapter 173 Network Analyzer 3 V sequence Measurements associated with the Network Analyzer function list and description in the dedicated chapter 106 V 3s sequence THD Current THD Voltage Counters Maintenance Contact wear Installation and maintenanc...

Page 29: ...er 6 Enable 5 Function enabling and parameters see the details in the dedicated chapter 106 Datalogger 6 Enable 5 Function enabling and parameters see the details in the dedicated chapter 104 Dual Setting 6 Enable 5 Enable function 65 Default setting Default setting configuration System Data Unit date configuration 115 Time Unit time configuration Language Menu language configuration New password ...

Page 30: ...d Protection unit Ekip Touch information Mainboard serial number Trip unit serial number type version regulation software version date and time language Circuit breaker CB Information TAG name CB name rated power number of poles CB status and position total operations IEC61557 12 1 Measurements status 1 from the Class 1 Power Energy Metering package serial numbers of the assembly and connected pow...

Page 31: ...ure 15 3 Pressing the Enter button selects the desired value The display automatically shows the submenu of the higher level and the changed parameter shows a confirmation check mark Figure 16 At this point it is possible to confirm the programming Step 4 or to access other parameters for further changes Step 1 4 Press the ESC button to return to the previous menu until the Programming page appear...

Page 32: ...peration requested which is the responsibility of the user whatever the command reset parameters display opening closing contacts Exceptions Before validating the change of a parameter the Trip unit performs a check of all its parameters to certify that there is no conflict or incorrect condition If the Trip unit detects an incorrect condition the details are shown on the display and the parameter...

Page 33: ...d allows access to all menus without having to re enter it repeatedly if the operations are carried out within a time of two minutes Once this time has elapsed it must be entered again where necessary NOTE the password also expires when a programming session is canceled page 31 Entering the password To enter the password it is necessary to confirm each digit using the Enter button changing the dig...

Page 34: ...for installation before startup TRIP With the Ekip CI module Ekip M Touch allows selecting a different TRIP configuration so that if tripped a contact of the Ekip CI module connected to an external contactor Normal mode is triggered NOTE for I and G protections the TRIP is always managed with a Trip Coil command For more details see the Ekip M Touch parameters page 66 References Many protection th...

Page 35: ...uit 38 G 1 Ground malfunction with adjustable delay 40 MCR Instantaneous short circuit when the circuit breaker closes 41 2I Programmable instantaneous short circuit 42 IU Power imbalance 43 Neutral 2 Different protection on the neutral phase 41 Harmonic distortion Distorted waveforms 44 T Abnormal temperatures 44 Hardware Trip Internal connection errors 44 Power thresholds Control thresholds exce...

Page 36: ...onds which are settable in a range 3 s 60 s with 1 s step 60 s Thermal memory Activates deactivates the thermal memory function see page 70 for details NOTE the function is always ON with Ekip M Touch trip unit and available for all the others Trip unit model with a curve t k I2 OFF Pre alarm I1 Enables a warning to be sent that the measured current is near the threshold triggering the protection ...

Page 37: ... Thermal memory Activates deactivates the thermal memory function see page 70 for details NOTE the function is available only with a curve t k I2 OFF Zone Selectivity Activates deactivates the function and the display availability of selectivity time see page 70 for details NOTE the function is available only with curve t k OFF Selectivity time This is the trip time of the protection with the zone...

Page 38: ... is expressed in seconds settable in a range 0 05 s 0 4 s with 0 01 s step 0 05 s Zone Selectivity Activates deactivates the function and the display availability of selectivity time see page 70 for details in the presence of both S and S2 active selectivity the input and output are shared with an OR function it is also sufficient for just one of the two to be active to stimulate inputs and output...

Page 39: ... details OFF StartUp threshold Protection threshold valid during Startup time in conditions in which the function is active see page 73 for details The value is expressed both as an absolute value Ampere and as a relative value In settable in a range 1 5 In 15In with 0 1 In step 1 5 In StartUp time This is the time for which the StartUp threshold is active calculated from tripping of activation th...

Page 40: ...NOTE with curve t k t4 can also be configured as instantaneous in this mode the trip time is comparable with the trip time declared for protection I see page 78 for details 0 4 s Pre alarm I4 Enables a warning to be sent that the measured current is near the threshold triggering the protection The value is expressed as a percentage of the threshold I1 which is settable in a range 50 I4 90 I4 with ...

Page 41: ...he selectivity type see page70 MCR Protection Function The protection is active for a calculated period of time starting from the change of state open closed then it turns off If during this period the current of one or more phases exceeds the I3 threshold after a fixed time that cannot be programmed the protection sends the TRIP command To verify and simulate the trip times based on all the param...

Page 42: ...figuration makes the function and delay parameters available Active the protection is always active Dependent function Function The activation event can be selected from the input contacts of Ekip Signalling 4K and Ekip Signalling 2K the unit status open closed and the Custom function NOTE Ekip Connect enables the Custom function to be customized to combine the activation event with up to eight st...

Page 43: ...and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as information OFF Version Enables the unbalance calculation method to be selected Old Sbil 100 x Imax Imin Imax New Sbil 100 x 100 x max Imi Imi NOTE max Imi maximum deviation between measured currents calculated by compari...

Page 44: ...he neutral threshold expressed as a multiplicative factor example InN 200 InN 2 Iu is the size of the CB Harmonic Distortion Allows activating an alarm in the event of distorted waveforms The protection can be enabled in the Measurements menu page 28 If enabled an alarm is activated for peak factors greater than 2 1 IMPORTANT the protection just manages the alert not the trip Protection T The T pr...

Page 45: ...age of the threshold I1 which is settable in a range 50 I1 100 I1 with 1 step 50 I1 Threshold I I2 Enable Activates protection and availability of protection threshold on menu OFF Threshold The value is expressed as a percentage of the threshold I1 which is settable in a range 50 I1 100 I1 with 1 step 75 I1 Threshold Iw1 Enable Activate protection and availability of protection threshold on menu O...

Page 46: ...ummary table with the operating characteristics page 79 Chart with tripping curve page 87 Parameters Parameter Description Default Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as information OFF Threshold U8 Defines the value that act...

Page 47: ...tion works like the UV Protection if one or more line to line voltages read by the unit falls below the U15 threshold for a time greater than t15 the protection sends the TRIP command It is independent of UV protection and it is therefore possible to program thresholds and functions of the two protections to take advantage of different system solutions example signaling with UV and opening command...

Page 48: ...time are managed only as information OFF Threshold U16 Defines the value that activates the protection The value is expressed both as an absolute value Volt and as a relative value Un settable in a range 1 Un 1 5 Un with 0 01 Un step 1 05 Un Time t16 This is the trip time of the protection the value is expressed in seconds which are settable in a range 0 05 s 120 s with 0 01 s step 5 s Constraints...

Page 49: ...ty on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as information OFF Threshold I14 Defines the unbalance value that activates the protection The unbalance is expressed as a percentage value and is calculated as follows Sbil 100 x max Umi Umi in a range 2 90 with 1 step NOTE max Umi maxim...

Page 50: ...vides a step variation based on the parameters Ul and Ks Lin linear provides a dynamic variation based on the parameters Ul Uh and Ks Figure 20 To verify and simulate the trip times based on all the parameters see Protection summary table with the formulas for calculations page 79 Chart with tripping curve page 89 Parameters Parameter Description Default Enable Enables disables protection and avai...

Page 51: ...ip threshold I21 Mod Voltage read Trip threshold Lin Uh and Ul The threshold varies gradually see above Uh I20 The value is expressed both as an absolute value Volt and as a relative value Un settable in a range 0 2 Un 1 Un with 0 01 Un step 1 Un Threshold Ks Threshold I20 calculation constant The value is expressed as a percentage value of the threshold I20 which is settable in a range 0 1 I20 1 ...

Page 52: ...trip times based on all the parameters see Protection summary table with the formulas for calculations page 79 Chart with tripping curve page 89 Parameters Parameter Description Default Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as ...

Page 53: ...s the TRIP command The protection is always available in 4P configuration To verify and simulate the trip times based on all the parameters see Protection summary table with the operating characteristics page 79 Chart with tripping curve page 89 Parameters Parameter Description Default Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivat...

Page 54: ...e Protection summary table with the operating characteristics page 79 Chart with tripping curve page 90 Parameters Parameter Description Default Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as information OFF Threshold f12 Defines the...

Page 55: ...ection works like the UF Protection if the grid frequency read by the unit falls below the f17 threshold for a time greater than t17 the protection sends the TRIP command It is independent of UF protection and it is therefore possible to program thresholds and functions of the two protections to take advantage of different system solutions example signaling with UF and opening command with UF2 or ...

Page 56: ...rotection summary table with the operating characteristics page 79 Chart with tripping curve page 90 Parameters Parameter Description Default Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as information OFF Threshold f18 Defines the va...

Page 57: ...trip times based on all the parameters see Protection summary table with the operating characteristics page 79 Chart with tripping curve page 91 Parameters Parameter Description Default Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as ...

Page 58: ...ow High 123 High Low 321 Low High 123 Low High 321 High Low 321 High Low 123 Low High 321 Low High 123 High Low 321 High Low 321 High Low 321 Low High 321 Low High To verify and simulate the trip times based on all the parameters see Protection summary table with the formulas for calculations page 79 Chart with tripping curve page 91 Parameters Parameter Description Default Enable Enables disables...

Page 59: ...e Ampere and as a relative value In settable in a range 0 6 In 10In with 0 1 In step 2 In StartUp time This is the time for which the StartUp threshold is active calculated from tripping of activation threshold set details on page 73 The value is expressed in seconds which are settable in a range 0 1 s 30 s with 0 01 s step 0 1 s Min Angle Direction Ekip touch calculates the phase displacement ang...

Page 60: ... service connector with Ekip Connect or with system bus communication it is also possible to access the block functions see page70 OP Protection Function If one or more active powers read by the unit exceeds the P26 threshold for a time greater than t26 the protection sends the TRIP command To verify and simulate the trip times based on all the parameters see Protection summary table with the oper...

Page 61: ...eactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as information OFF Threshold P23 Defines the value that activates the protection The value is expressed both as an absolute value kW and as a relative value Sn settable in a range 0 1 Sn 1 Sn with 0 001 Sn step 1 Sn Time t23 This is the trip time of the protection the value is expressed in sec...

Page 62: ...efault Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as information OFF Kq Threshold Defines the slope of the straight line in relation to the threshold Q24 The value is expressed as an absolute value angular coefficient of the straigh...

Page 63: ... below the threshold Vmin is present the protection is not active The value is expressed both as an absolute value Volt and as a relative value Un settable in a range 0 5 Un 1 2 Un with 0 01 Un step 0 5 Un Constraints limitations and additional functions Ekip Touch accepts parameters with the following limitations Q24 Q25 and Kq Kq2 From the service connector with Ekip Connect or with system bus c...

Page 64: ...rs Parameter Description Default Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only as information OFF Threshold f28 Defines the maximum permitted frequency fluctuation rate over the time if the limit is exceeded protection is tripped The v...

Page 65: ... different protection configurations one as an alternative to the other managing the setting changes with programmable events The function can be activated in the Settings Dual Setting menu page 29 Parameter Description Default Enable Activates deactivates the function OFF Default set Defines the main set of protections and the secondary set of protections which is activated in the presence of the...

Page 66: ...trip time L Time t1 The start up time Motor start up calculated from when at least one phase exceeds the fixed threshold of 0 25 x I1 during which some protections are inhibited The reset time from thermal memory L following a TRIP tmem res Motor Class t1 s Motor start up s tmem res min 5E 12 3 5 10E 22 5 10 20E 45 10 20 Figure 24 NOTE 1 temporary shutdown during Motor Start up is valid and active...

Page 67: ...ector with Ekip Connect or with system bus communication it is also possible to access the block functions see page 70 R STALL Protection Function R Stall protects against motor blocks but in contrast with R Jam it is not inhibited during Motor Start up if the current of one or more phases exceeds the Ir threshold for a time greater than tr the protection is activated and sends the TRIP command To...

Page 68: ...tion Function U protects the motor in case of loss of a phase if the rms value of at least one phase falls below the threshold of 0 1 In and at the same time at least one current is greater than 0 25 for a time greater than tu the protection sends the TRIP command The protection is inhibited during Motor start up If the U protection alarm occurs during Motor start up the trip unit calculates the t...

Page 69: ...trolling the motor temperature If the measured temperature exceeds the value of 120 C for more than one second the protection sends the TRIP command Parameters Parameter Description Default Enable Enables disables protection and availability on menu of the parameters OFF Trip Enable Activates deactivates the open command if disabled the alarm and the lapsing of the protection time are managed only...

Page 70: ...he trip time NOTE the function changes the trip time even in the event of overloads that do not lead to the opening command Zone selectivity S S2 and G Preface The function which can be activated for the S S2 and G protections if available and enabled allows connecting several devices belonging to the same system including Ekip Touch to better manage the trip commands in case of S S2 e G protectio...

Page 71: ...he parameters of the protections to avoid unwanted openings Condition Szi Szo Tripping time Comments If I2 0 0 No TRIP The device is not in alarm status If I2 1 1 No TRIP The device is not in alarm status but transmits the selectivity signal received from the device upstream If I2 0 1 t2 sel The device is in alarm status and is the first to detect the fault trips in the time t2 sel If I2 1 1 t2 Th...

Page 72: ...f the direction of the malfunction is the same as the direction of reference see page 58 for details then the Forward output is activated If instead the direction is contrary the Backward output is activated Fault direction Condition DFin Dbin DFout Dbout Tripping time Comments Forward If I7 Fw 0 x 0 x No TRIP The device is not in alarm status Backward If I7 Bw x 0 x 0 Forward If I7 Fw 1 x 1 x No ...

Page 73: ... is possible to select the activation event of the zone selectivity input or output IMPORTANT in the Custom configuration the only event to activate zone selectivity is the one set and therefore the standard selectivity operation is not active change recommended only for expert technical staff Startup The function which can be activated for S I G S2 D and UP protections if available and enabled al...

Page 74: ...ctions that have blocks are S I G MCR S2 D S V S2 V UV OV VU UV2 OV2 UP OP RP RQ OQ RV UF OF UF2 OF2 ROCOF UC U R Jam R Stall IMPORTANT blocks can cause Increase in trip times max 30 ms due to the verification of the event itself example frequency control Unwanted deactivation of the protection if the block is associated with states or module signals on the local bus and the auxiliary power supply...

Page 75: ...Sends a close command it s necessary the presence of MOE E Switch On LOCAL Configuration change from Remote to Local Settings Modules Functions 29 Signalling RESET Reset contacts of signalling modules Parameters Each command has two programmable parameters Parameter Description Default Function One or several events up to eight in AND or OR logic configuration to activate command The Custom config...

Page 76: ...signals In this configuration if the function is enabled for S protection and it is in an alarm state the hardware block signal S D Forward and the S logical selectivity bit are activated at the output Based on the block signals If the S D Forward hardware block signal and the S2 logical selectivity bits of actor 1 are not active at the input the opening command is sent according to the selectivit...

Page 77: ...correctly receives the message on its input otherwise it signals an error If the hw input is active the diagnostic is not performed if the input configured for diagnostics is active at the time of the test the diagnostic is not performed and the parameter Detection status in the Ekip Link Status page shows Unknown Logical Selectivity errors and inconsistency Regardless of the diagnostics if a hard...

Page 78: ... Trip threshold tolerance 3 Trip time tolerance L 49 Curve t k I2 𝑡𝑡 𝑡1 𝑥 9 𝐼𝑓 𝐼1 2 Activation for If in the range 1 05 1 2 x I1 10 with If 6 x In 20 with If 6 In Curves 60255 151 𝑡𝑡 𝑡1 𝑥 𝑎 𝑥 𝑏 𝐼𝑓 𝐼1 𝑘 1 S 50TD 51 Curve t k tt t2 7 with If 6 In 10 with If 6 In The better of 10 or 40 ms Curve t k I2 𝑡𝑡 𝑡2 𝑥 100 𝐼𝑓2 15 with If 6 x In 20 with If 6 In S2 50TD tt t5 7 with If 6 In 10 with If 6 In The b...

Page 79: ...12 t17 1 5 The better of 100 ms with t12 5 s 10 min 30 ms or 40 ms with t12 5 s OF 81H OF2 87H tt t13 t18 1 5 The better of 10 or 40 ms with t13 5 s 100 ms t13 5 s Power Protections Protection ANSI code Trip time tt Trip threshold tolerance 3 Trip time tolerance UP 32LF tt t23 10 the better of 10 or 40 ms with t23 5 s 100 ms with t23 5 s OP 320F tt t26 10 the better of 10 or 40 ms with t26 5 s 100...

Page 80: ...its If conditions are not guaranteed the tolerances in the table following the notes are valid 4 The trip unit considers a hysteresis of 3 for exiting the alarm condition 5 Tolerance valid for frequencies in the range fn 2 For frequencies outside the range there is a tolerance of 5 6 20 for the 0 4 Hz s threshold 7 Time to be considered valid after the Motor start up 8 Time to be considered valid ...

Page 81: ...ing the maximum and minimum values of the parameters of each protection The protections that have multiple curves e g protection S are represented in multiple charts The curves do not take into account the effects of special parameters like thermal memory and startups NOTES to calculate the trip time it is recommended to always use the mathematical function in the protections summary table page 78...

Page 82: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 82 L curve IEC 60255 151 SI L curve IEC 60255 151 VI ...

Page 83: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 83 L curve IEC 60255 151 EI L curve t k I4 ...

Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...

Page 85: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 85 S curve t k Curve S2 I curve MCR curve 2I curve ...

Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...

Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...

Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...

Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...

Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...

Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...

Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...

Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...

Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...

Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...

Page 96: ...ase and ground fault currents expressed in effective value The measurement range and the performance depend on the rated current defined by the rated size of the Trip unit Measurement Measurement range min max Normal operating range Accuracy of detected value 1 Phase currents 0 03 64 In 0 2 1 2 In 1 3 Ground fault current 2 0 08 64 In 0 2 1 2 In 2 3 NOTES 1 Accuracy referring to normal operating r...

Page 97: ...vent reported for informational purposes Timing of a protection in progress trip pending Alarm referring to a non dangerous condition Operating alarm malfunction or connection error Openings Ekip Touch is able to log the last 30 TRIPs The complete list is available in the Measurements Log Openings menu where each trip includes the following useful information The protection that triggered the open...

Page 98: ...ess the iTEST button four times Min Max measurements In the Measurements Logs Measurements menu the Ekip Touch records the maximum and minimum phase currents The recording interval between one measurement and the next can be set with the parameter Measurement interval Measurement interval available in the Settings menu page 29 The Enter ESC Right Up and Left Down buttons can be used to scroll thro...

Page 99: ...the last maintenance value Two areas are available in Trip unit menus Activation area Settings Maintenance menu allows activating the Maintenance function Measurements and reset area Measurements Maintenance menu appears only if the Maintenance function is activated Provides information on the maintenance contact wear and dates and the command to confirm the maintenance confirming the current date...

Page 100: ...l time measurements Real time voltages available in the Summary pages are the real time measurements of line to line and phase voltages expressed in effective value The display measurement range and performance depend on the rated voltage set Un Real time powers available in the Summary pages are the real time measurements of the total and phase active powers The display measurement range and perf...

Page 101: ...ble to record described on page 97 for current protections The voltage frequency or power protection that trips determines the measurements recorded at the time of opening Protection Measurements recorded Remarks Voltage Currents L1 L2 L3 Ne voltages U12 U23 U31 U0 Ne is available with CB 4P and 3P N U0 is available in the event of trips for RV protection Frequency L1 L2 L3 Ne currents and grid fr...

Page 102: ...and or reactive power not available or outside the permitted ranges NOTE Accuracy referring to Ekip Touch and Ekip Touch Measuring without Class 1 Power Energy Metering package If the Class 1 Power Energy Metering package is present and for all other Trip unit models check the performance shown on page 103 Energy counters Energy counters are the total active reactive and apparent energy measuremen...

Page 103: ...ension and class 2 Available with LSIG versions 3 Available for voltages greater than 30 V with Un 277 V or 60 V with Un 277 V 4 45 55 Hz with fn 50 Hz 54 66 Hz with fn 60 Hz 5 Pmin 0 5 In x 5 V Pmax 3 x 16 In x 690 V Functional characteristics The measurement performance of the Class 1 Power Energy Metering package are guaranteed in the following conditions from table 43 of the IEC61557 12 standa...

Page 104: ...ction requires the presence of auxiliary voltage Figure 26 Parameters 1 The function parameters and commands are available in the Settings Datalogger menu page 29 Parameter Description Default Enable Enable disable the function and the availability of the parameters in the menu NOTE the enable command is hidden with at least one datalogger activated OFF Datalogger Num Determines the number of logs...

Page 105: ...ven if switched off The internal battery life of the unit may decrease considerably with respect to the declared value in cases where there is a log in the memory and there is no auxiliary power supply Volatile Ekip Touch loses the log if switched off When the unit is switched back on the data logger automatically restarts having lost the previously stored data The parameter is set to Non volatile...

Page 106: ...rs in the menu OFF I Harmonic Analysis Activates the harmonic analysis of the currents OFF V Harmonic Analysis Activates the harmonic analysis of the voltages OFF V Low Threshold Counter control threshold Under V Th The value is expressed as a percentage of the rated voltage Un which can be set in a range of 75 95 Un with 5 steps 85 Un V High Threshold Counter control threshold Over V Th The value...

Page 107: ... thresholds are expressed as a percentage of the rated voltage Un which can be set in a range of 105 125 Un with 5 steps All times are expressed in seconds settable in a range of 0 04 s to 60 s with variable steps Parameter Description Default V swell Th Short Counter control threshold Swell Short 125 Un V swell dur Short Minimum duration of the swell above the Short threshold to validate the coun...

Page 108: ...tal list Counters Sequences Description Last time stamp Date and time referred to the last record of the sequences Counters Unbalance Description Last value Voltage imbalance related to the current period Actual unbalance value Voltage imbalance related to the previous period Last time stamp Date and time referred to the last record of imbalances Actual number of U Counts the times when the mean v...

Page 109: ...lock Counters Undervoltage Description Last time stamp Date and time referred to the last Under V Th counter record Last value Value of the last sag below the Under V Th threshold V Actual number of O Count of Under V Th referring to the current day Actual day 2 day 7 number of O Count of Under V Th detected in the last seven days of activity calculated using the unit s internal clock V Interrupti...

Page 110: ...nal clock Sags In the Counters Day 1 and Counters Cumulative submenus some counters for sags are available Counters Description Sag Short Counts the times that any line to line voltage drops below the V sag Th Short threshold for longer than V sag dur Short Sag Middle Counts the times that any line to line voltage drops below the V sag Th Middle threshold for longer than V sag dur Middle Sag Long ...

Page 111: ...t threshold for longer than V swell dur Short Swell Long Counts the times in which any line to line voltage exceeds the threshold V swell Th Long for longer than V swell dur Long The count refers to the interval of the menu of reference previous day or cumulative NOTE since it is possible for an event to fall within more than one type only the counter related to the highest applicable type is incr...

Page 112: ...minutes 45 days It is possible to reset them with a command from the service connector via Ekip Connect or with a communication from the system bus Supplemental list Counters THD Current Description Actual minutes Count of THD Current referring to the current day min Actual day 2 day 7 number of THD C Count of THD Current referred to the last seven days of activity calculated using the unit s inte...

Page 113: ...t be made without protection alarms Configuration The Circuit breaker Configuration menu is available with CB 3P which allows activating the presence of the external neutral sensor described on page 204 Activation of the configuration with external neutral 3P N enables Histogram of the Ne phase on the Histograms page Neutral current measurements Submenu for configuring the Neutral protection Loggi...

Page 114: ... Functions Access to the functions Switch On LOCAL and RESET signal see page 75 BLE The menu in Settings Modules allows activating the Bluetooth antenna on the Trip unit useful for communicating with an external device tablet smartphone using the BLE protocol through the Ekip Connect Mobile app page 12 These are the available parameters Parameter Description Default Enable Enables disables the act...

Page 115: ...age Set the language in the display menus English Password Set the password see page 33 for details 00001 IMPORTANT setting and checking the Date and Time is important for all logging functions trip or measurements If there is a malfunction with the date and time reset and if necessary replace the Ekip Touch battery see 1SDH001000R0509 View The View menu allows access to the configuration of the C...

Page 116: ...ion In Normal mode if the Trip unit detects a malfunction even after the opening command at O61 a command is also sent to the CB Trip coil Normal Autoreclosure Activated With Open Mode Normal allows reclosing of contact O61 following a TRIP for L On protection Off Motor Class Allows selecting the motor trip class page 66 for operating details between 5E 10E 20 E 30E Contactor Delay Defines the wai...

Page 117: ...e of the trigger Off Delay state deactivation delay calculated from when the trigger no longer exists NOTE the status is activated if the trigger is present for a time set in On Delay and is deactivated if the trigger is absent for a time longer than the Off Delaysetting Figure 29 The states can be used with the external Ekip Signaling 10K module on Link Bus or with the programmable functions to r...

Page 118: ...AND programmable functions and the commands Request circuit breaker open and Request circuit breaker close Change Dual Setting of parameters always If activated it allows changing the parameter settings Adaptive Protections also with timing alarms in progress Disabled by default Repeat zone selectivity S G HW If Enabled the propagation logic of the zone selectivity HW signals is valid according to...

Page 119: ... is sent to the CB Trip coil IMPORTANT the opening command is sent with the circuit breaker closed and no current flowing following a command the verification of the effective change of the actuator status and of the information on the display are delegated to the user make sure that no alarms are noted on the diagnostic bar before performing the test NOTE to reset the TRIP signal press the iTEST ...

Page 120: ...ntacts and LEDs and input test LED and includes the following operations 1 Reset output contacts open and LEDs off 2 Turn on all the LEDs in sequence output and input 3 Closure and shutdown of the two output contacts in sequence switching on the relative LEDs 4 Restore initial conditions IMPORTANT the Self test command closes the contacts regardless of the configuration set by the user the safety ...

Page 121: ...Load 15 It is possible to choose between Automatic or Manual configuration Manual Powers Limits Allows setting the 10 power limits from Power Limit 1 to Power Limit 10 The value is expressed in kW and can be set in a range of 10 kW 10000 kW with 10 kW steps 10 kW NOTE to set all the parameters of the function it is recommended to first configure the parameters via Ekip Connect and only then work o...

Page 122: ...nu OFF Version Display of the function version Basic or Adaptive E NOTE with the Basic version the only parameter available is Reconnection Timeout Solar System Present Defines if the microgrid includes a solar system Off On Off Solar rated power Available with Solar System Present On defines the rated power of your solar system The value is expressed in kW which can be set in a range 100 kW 65535...

Page 123: ...red Fn Rated frequency of the Trip unit LOADS Number of controlled loads LOADS Shed Number of loads shed With Power Controller activated the Load Shedding menu is available in the Information page page 30 and it provides information on the 15 loads in 2 submenus Submenu Information included Load Input Status Load status from Load 1 to Load 15 open or closed Active load Load configuration from Load...

Page 124: ...FF Trip enabling Activate deactivate the sending of the opening command If disabled the alarm and the exceeding of the protection time are managed only as information OFF Threshold Defines the value that triggers the protection The value is expressed both in an absolute value Volt and a relative value Un which can be set in a range 1 Un 1 3 Un with 0 05 Un steps 1 1 Un Time The trip time The value...

Page 125: ...l is activated The control threshold submenu is available in the Protections Advanced Warnings menu where the following parameters can be set Parameter Description Default Enable Enable disable the control and the availability of the parameters in the menu OFF Signal source Defines whether the line to line voltages to be checked are those from the internal sockets Measuring or from the Ekip Synchr...

Page 126: ...efines the lower value of the control band expressed both in an absolute value Hertz and a relative value Fn which can be set in a range 1 Fn 1 1 Fn with 0 001 Fn steps 1 002 Fn Time The voltage control time to activate the signal The value is expressed in seconds which can be set in a range 0 1 s 900 s with 0 1 s steps 30 s F W1 Warning If the frequency measured by the Trip unit exceeds or falls ...

Page 127: ...d output contact working CB in disconnected position 1 3 Synchronism not available 4 Communication partially active 5 Inputs and output contacts partial available 6 Output contact mantiene la posizione precedente NOTE 1 The description refers to the module when correctly on and with the CB in the indicated position 2 In the Test position the trip unit is connected to the modules and all informatio...

Page 128: ...for supplementing Ekip Touch in the communication networks that are available with the specific Ekip Com module and an IMPORTANT file with notes on the use of the files File Ekip Com Protocol Module ABBS0E7F gsd EkiDPB bmp File gsd and picture for configuring Ekip Com Profibus DP Ekip_COM_EtherNetIP_M4_v03_06 eds File eds for configuring Ekip Com EtherNet IP Ekip_COM_DeviceNet_v02_08 eds File eds ...

Page 129: ...Connections Ekip Cartridge has two terminal blocks Figure 30 Connector Description 1 Terminal for connecting the engaged disengaged status contact NOTE by default Ekip Cartridge is supplied with a jumper on the terminal block To use the engaged disengaged status signal remove the jumper from the connector and connect the cables coming from the fixed part of the CB 2 Terminal for the connection of ...

Page 130: ...supply On steady beam powered up Electrical specifications Model Ekip Supply 24 48VDC Ekip Supply 110 240 VAC DC Supply voltage 21 5 53 VDC 105 265 VAC DC Frequency 45 66Hz Maximum power consumption without accessories 1 3 W 3 VA W Maximum power consumption with accessories 2 10 W 10 VA W Maximum inrush current 2 A for 20 ms 2 A for 20 ms NOTE 1 Ekip Touch with Ekip Supply only 2 Ekip Touch with t...

Page 131: ... with two different modules that are compatible with the Modbus RTU protocol Ekip Com Modbus RTU and Ekip Com Modbus RTU Redundant The two modules are identical in terms of characteristics and installation methods except for display menus on unit cablings and addresses for external communication that are specific for each model NOTE if not specified the information in the following chapter applies...

Page 132: ...s RTU communication not active on with fast flashing Modbus RTU communication active Tx Indicates the status of the communication between the network master and the module slave off communication between Modbus RTU not active on with fast flashing Modbus RTU communication active Configurations Resistances can be linked to bus RS 485 configuring dip switches located on the side of the module Figure...

Page 133: ...p and parity bit 4 options available 8 E 1 8 bit datum 1 EVEN parity bit 1 STOP bit 8 O 1 8 bit datum 1 ODD parity bit 1 STOP bit 8 N 2 8 bit datum no parity bit 2 STOP bits 8 N 1 8 bit datum no parity bit 1 STOP bit 8 E 1 NOTE 247 default of the module Ekip Com Modbus RTU 246 default of the module Ekip Com Modbus RTU Redundant Remote configurations From the service connector via Ekip Connect or w...

Page 134: ...nt modules that are compatible with the Profibus protocol Ekip Com Profibus DP and Ekip Com Profibus DP Redundant The two modules are identical in terms of characteristics and installation methods except for display menus on unit cablings and addresses for external communication that are specific for each model NOTE if not specified the information in the following chapter applies to both models B...

Page 135: ...master and module not active fixed light communication between master and module active Tx Indicates the status of the communication between the network master and the module slave off communication between master and module not active flashing light communication between master and module active Configurations Resistances can be linked to bus RS 485 configuring dip switches located on the side of...

Page 136: ...the Modules Settings menu in which the following communication parameters can be configured Parameter Description Default Serial address Module address range from 1 to 125 available IMPORTANT devices connected to the same network must have different directions 125 124 NOTE NOTE 125 default of the module Ekip Com Profibus DP 124 default of the module Ekip Com Profibus DP Redundant Remote informatio...

Page 137: ...es are identical in terms of characteristics and installation methods except for display menus on unit cablings and addresses for external communication that are specific for each model NOTE if not specified the information in the following chapter applies to both models Both modules can be connected simultaneously to Ekip Touch to increase the potential of unit for example for applications in whi...

Page 138: ...he communication on bus Off no error Fixed light device in bus off or Network Power absent condition Flashing light I O connection cyclical data in timeout NOTE the device has not yet sent the in line Duplicate ID sequence Configurations Resistances can be linked to the CAN bus configuring dip switches located on the side of the module Figure 36 Resistances Dip Description Default Rterm 1 and 2 Te...

Page 139: ... 3 options available 125 kbit s 250 kbit s 500 kbit s 125 kbit s NOTE 63 default of module Ekip Com DeviceNetTM 62 default of module Ekip Com DeviceNetTM Redundant Remote configurations From the service connector via Ekip Connect or with communication by system bus it is possible to access additional parameters Parameter Description Default Class ID Defines the addressing class of the module betwe...

Page 140: ... 320 udp 68 udp DHCP client DHCP client enables alternatively to static address On To connect Ekip Com Modbus TCP to Ekip Touch the Ekip Cartridge page 129 and Ekip Supply page 130 accessories are required Safety As the module enables the actuator to be controlled that is connected to Ekip Touch and enables unit data to be accessed it can be connected only to networks meeting all the necessary sec...

Page 141: ...nnect the module to its communication network and for terminal references For the communication bus a Cat 6 S FTP cable must be used Cat 6 with double S FTP shield the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and Ekip Touch Supply Ekip Com Modbus TCP is supplied directly by the Ekip Supply module to which it is connected NOTE in the absence of an auxiliary supply the...

Page 142: ...ff Static IP address Enables static IP to be selected 0 0 0 0 Static Network Mask Enables the subnet mask to be selected 0 0 0 0 Static Gateway address Enables in the presence of several subnets the IP address of the node to which the module is connected to be selected 0 0 0 0 Information on menu If the module is detected correctly by Ekip Touch the following information is available on the About ...

Page 143: ... selected whether there is daylight saving time ON or not OFF in the country to which the synchronization time refers OFF Disable Gratuitos ARP Permits Enabled ARP the periodic generation of a Gratuituos ARP message to be enabled that is used by Ekip Connect to find rapidly the modules with Ethernet scanning without its IP address being known beforehand ARP enabled Access protected by password Ena...

Page 144: ...C To connect Ekip Com Profinet to Ekip Touch the Ekip Cartridge page 129 and Ekip Supply page 130 accessories are required Safety As the module enables the actuator to be controlled that is connected to Ekip Touch and enables unit data to be accessed it can be connected only to networks meeting all the necessary security and unauthorized access prevention requirements e g the control system networ...

Page 145: ...nect the module to its communication network and for terminal references For the communication bus a Cat 6 S FTP cable must be used Cat 6 with double S FTP shield the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and Ekip Touch Supply Ekip Com Profinet is supplied directly by the Ekip Supply module to which it is connected NOTE in the absence of an auxiliary supply the co...

Page 146: ...out Modules menu Information Description SN and version Identification and SW version of the module MAC Address Address assigned by ABB with OUI Organizationally Unique Identifier equal to ac d3 64 that identifies uniquely the manufacturer of an Ethernet device Remote information From the service connector via Ekip Connect or with a system bus communication additional information is available on t...

Page 147: ...1 68 udp DHCP Client DHCP client enables alternatively to static address On To connect Ekip Com EtherNet IP to Ekip Touch the Ekip Cartridge page 129 and Ekip Supply page 130 accessories are required Safety As the module enables the actuator to be controlled that is connected to Ekip Touch and enables unit data to be accessed it can be connected only to networks meeting all the necessary security ...

Page 148: ...to connect the module to its communication network and for terminal references For the communication bus a Cat 6 S FTP cable must be used Cat 6 with double S FTP shield the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and Ekip Touch Supply Ekip Com EtherNet IPTM is supplied directly by the Ekip Supply module to which it is connected NOTE in the absence of an auxiliary su...

Page 149: ...onnected 0 0 0 0 Information on menu If the module is detected correctly by Ekip Touch in the About Modules menu the following information is available Information Description SN and version Identification and SW version of the module IP address Address of the module assigned to the module by a DHCP server at the moment of the connection to the network in the event of configuration with dynamic IP...

Page 150: ... server to be set that supplies SNTP 0 0 0 0 Time zone Defines the time zone to be used for synchronism 00 00 Daylight Saving Time Enables it to be selected whether there is daylight saving time ON or not OFF in the country to which the synchronization time refers OFF NOTE Enable IEEE 1558 and Enable SNTP client must not be enabled simultaneously Remote information From the service connector via E...

Page 151: ...ddresses Depending on the parameters set which are illustrated on subsequent pages the following module ports are used Ethertype Port Protocol 0x0800 IP 102 ISO Transport Service on top of the TCP RFC 1006 0x88B8 GOOSE Messages 0x0800 IP 123 UDP NTP Network Time Protocol 0x0800 IP 69 UDP TFTP Trivial File Transfer Protocol To connect Ekip Com IEC 61850 to Ekip Touch the Ekip Cartridge page 129 and...

Page 152: ...t the module to its communication network and for the terminals references For the communication bus a Cat 6 S FTP cable must be used Cat 6 with double S FTP shield the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and Ekip Touch Supply Ekip Com IEC 61850 is supplied directly by the Ekip Supply module to which it is connected NOTE in the absence of an auxiliary supply the...

Page 153: ...network server to be set that supplies SNTP 0 0 0 0 Information on menu If the module is detected correctly by Ekip Touch in the About Modules menu the following information is available Information Description SN and version Identification and SW version of the module IP address Address of the module assigned to the module by a DHCP server at the moment of the connection to the network in the eve...

Page 154: ...for synchronism 00 00 Daylight Saving Time Enables it to be selected whether there is daylight saving time ON or not OFF in the country to which the synchronization time refers OFF TFTP Security level Defines the file loading procedure TFTP always On port open loading still possible TFTP enable required port normally closed to start loading the Enable TFTP command must be run at the start of the p...

Page 155: ...with the SNTP server SNTP Server Synchronisation Synchronism status with SNTP server IEEE 1558 status Valid with IEEE 1588 Master ON communicates the presence Slave or PTP Master Active or absence PTP Master but Passive of a higher level master GOOSE Missing Signals whether an expected GOOSE has been received Configure Mismatch A received GOOSE does not comply with the expected structure Decode Er...

Page 156: ...that declare on the data sheet the support to the level L2 multicast If the network also comprises routers the multicast must be enabled and configured on all the level L3 VLAN interfaces Programmable logic With the Programmable Logic function it is possible to program the activation up to four bits of the Ekip Link each bit according to any combination of the status bits of an actor whose IP addr...

Page 157: ... selectivity information For more information on the Zone Selectivity function with Ekip Link see page 76 Connections Consult the electrical diagrams for 1SDM000068R0001 to connect the module to its communication network and for the terminals references For the communication bus a Cat 6 S FTP cable must be used Cat 6 with double S FTP shield the instruction sheets 1SDH002009A1503 to connect the mo...

Page 158: ...ed 0 0 0 0 Information on menu If the module is detected correctly by Ekip Touch in the About Modules menu the following information is available Information Description SN and version Identification and SW version of the module IP address Address of the module assigned to the module by a DHCP server at the moment of connection to the network in the event of configuration with dynamic or settable ...

Page 159: ...be enabled that is used by Ekip Connect to find rapidly the modules with Ethernet scanning without its IP address being known beforehand ARP enabled Access protected by password Enables the writing operations conducted by the network to be protected by a password password request Standard mode TCP Modbus password With access protected by enabled password this is the password to use before each wri...

Page 160: ...ver Synchronisation Synchronism status with SNTP server IEEE 1558 status Valid with IEEE 1588 Master ON communicates the presence Slave or PTP Master Active or absence PTP Master but Passive of a higher level master Remote Link information Further link function parameters are available Information Description Line Congruency detection Information on status and unsuitability of HW and logic selecti...

Page 161: ...s customer s sole responsibility to provide and continuously ensure a secure connection between the module and customer network or any other network as the case may be customer shall establish and maintain any appropriate measures such as but not limited to the installation of firewalls application of authentication measures encryption of data installation of anti virus programs etc to protect the...

Page 162: ...ected correctly by Ekip Touch in the Settings Modules menu the following communication parameters can be configured Parameter Description Default Enable Switches on switches off the communication between module and server Static IP address ON Defines whether the module has the dynamic IP address Off or static IP address On If On all associated parameters are enabled Off Static IP address Enables t...

Page 163: ...d by ABB with OUI Organizationally Unique Identifier equal to ac d3 64 that identifies uniquely the manufacturer of an Ethernet device Remote configurations From the service connector via Ekip Connect or with communication by system bus it is possible to access additional parameters Parameter Description Default CRL Enable Enables the CRL Certificate Revocation List to check the validity of the se...

Page 164: ...executable file Configuration error error status of the module configuration Sample time period of acquisition of data from the connected devices Log time period within which the acquired data are saved inside the log Upload time period calculated by module that occurs between each data transmission Configured device Number of modules involved in the network with Hub module API events polling peri...

Page 165: ...kip Touch can be installed only one module per type it is not admitted the connection of two or three equal modules for example two Ekip Signalling 2K 3 Connections Consult the electrical diagrams for 1SDM000068R0001 for terminal references for external cabling AWG 22 16 cables with a maximum external diameter of 1 4 mm must be used the instruction sheets 1SDH002009A1503 to connect the module to E...

Page 166: ...coil 1000 VAC 1 minute 50 Hz NOTE data on a resistive load Interface The module has three signalling LEDs Figure 43 LED Description Power Reports ON status and correct communication with Ekip Touch off module off fixed or flashing light synchronized on power LED of Ekip Touch module ON and communication with Trip unit present flashing not synchronized with power LED of Ekip Touch two fast flashes ...

Page 167: ...ay is expressed in seconds which are settable in a range 0 s 100 s with 0 01 s step NOTES if the source is deactivated before this time the output is not switched with delay 0 s the source must be anyway present for more than 300 S 0 s Contact type Defines the rest status of the contact with a non present source between open NO and closed NC NO Latched Enables the output and relative status LED to...

Page 168: ...n Off and of the outputs Open Closed Test If the Ekip Signalling 2K module is detected correctly the test area in the Test menu is activated For details of test characteristics see page 120 Remote information From the service connector via Ekip Connect or with a system bus communication additional information is available on the version and the status of the module HW and Boot version CRC status c...

Page 169: ...s than or the same as a maximum 0 5 Un default for a minimum time 1 s default the synchronism is considered to be reached if the differences between the RMS values the frequencies and the voltage phases are less than or the same as a maximum 0 12 Un 0 1 Hz and 50 default Dead busbar and configuration Normal Operation with one of the voltages nil the synchronism search is started up if the internal...

Page 170: ...oltage 0 120 VAC 10 120 VAC 1 1 Frequency 2 30 80 Hz 30 80 Hz 0 1 3 Phase 4 180 180 1 NOTES 1 with busbar active 2 with busbar active the measurement of the frequency starts with 36 VAC measured voltage and stops with 32 VAC measured voltage 3 in the absence of harmonic distortion 4 measurement of the phase refers to the phase difference between internal and external voltage 5 The accuracy values ...

Page 171: ...l 1000 VAC 1 minute 50 Hz NOTE data on a resistive load Interface The module has two signalling LEDS Figure 44 LED Description Power Reports ON status and correct communication with Ekip Touch off module off fixed or flashing light synchronized on power LED of Ekip Touch module ON and communication with Trip unit present flashing not synchronized with power LED of Ekip Touch two fast flashes per s...

Page 172: ...z step 0 1 Hz Delta Phase 4 Maximum difference between internal and external phase third synchronism condition The value is expressed in degrees which are settable in a range 5 50 with 5 step 50 Dead bar configuration With dead busbar and generator Reversed Ekip Synchrocheck external contacts connected to the generator Normal Ekip Synchrocheck external contacts connected to the network Normal Auto...

Page 173: ...ns not fulfilled or function disabled Frequency OK frequency synchronism condition fulfilled Not OK frequency synchronism condition not fulfilled or synchronism function disabled or frequencies outside measurement range Synchronism condition for frequencies is not available e g for operation with dead busbar Voltage OK Voltage synchronism conditions fulfilled Not OK Voltage synchronism conditions ...

Page 174: ...able e g because of disabled synchronism or operation with dead busbar or frequencies outside measurement range NOTES 1 the measurement accuracy of the voltage difference is 10 unless the parameter value is 0 02 Un in which case accuracy is 20 2 the characteristics of voltage and frequency measurements coincide with those declared on internal inputs page 96 Summary Page The summary page is activat...

Page 175: ...th two modules of the same model is not permitted e g two Ekip Signalling 3T 1 modules Connections Inputs Consult the electrical diagrams for 1SDM000068R0001 for terminal references the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and Ekip Touch For the PT1000 sensors use insulated cables for temperature sensors like PENTRONIC TEC SITW 24F TX type or the like with maximu...

Page 176: ...d measurement valid flashing input enabled sensor not connected and or measurement not valid Access from display If the Ekip Signalling 3T module is detected correctly the following areas became available on the trip unit Measurements page accessible from Home see page xx containing the measurements of all the PT1000 inputs and 4 20mA current loops of both 3T 1 and 3T 2 modules information submenu...

Page 177: ...whether the alarm is triggered by the measured value exceeding up or falling below down the set THR 1 threshold Down PT1000 1 THR 1 Alarm threshold THR 1 of the PT1000 1 input The value is expressed in degrees Celsius C which are settable in a range 40 C 240 C with 0 1 C step NOTE the Current Loop 4 20mA input thresholds are expressed as a percentage settable in a range 0 100 with 0 1 step each st...

Page 178: ...the module to Ekip Supply and Ekip M Touch IMPORTANT the I61 input is not isolated regardless of the system voltage the customer must ensure the insulation between the input and power supply of the Ekip Supply module according to the application and grid Supply Ekip CI is powered directly by the Ekip Supply module it is connected to NOTE without an auxiliary power supply the communication between ...

Page 179: ...ity configured by the user State Electrical condition Polarity Status detected and command Open Circuit open Active open On O61 open command Active closed Off Closed Short circuit Active open Off Active closed On O61 open command The re closing command is activated on the front Interface The module has four signaling LEDs Figure 46 LED Description Power Signals the status of power on and correct c...

Page 180: ...tact O61 The delay is expressed in seconds which can be set in a range 0 s 100 s with 0 01 s steps NOTES If the input is deactivated before this time has elapsed the re opening command is not sent With delay 0 s the input must still be present for more than 300 S 0 1 s Measurements If Ekip CI is correctly detected by Ekip Touch the specific area for the module is made available in the Measurements...

Page 181: ...ed IMPORTANT each XT2 XT4 circuit breaker can accommodate only one module configuration with external communication modules is not permitted if an internal module is present Features Ekip Com Modbus RTU integrates the following features Integrated status contacts Open Closed and Trip Backup battery to maintain the Date Time in the event of absence of auxiliary alimetry NOTA refer to document 1SDH0...

Page 182: ...figuration in the Modules Settings menu in which the following communication parameters can be configured Parameter Description Default Serial address Module address range from 1 to 247 available IMPORTANT devices connected to the same network must have different directions 247 246 NOTE Baudrate Data transmission speeds 3 options available 9600 bit s 19200 bit s 38400 bit s 19200 bit s Physical pr...

Page 183: ...atic address On IMPORTANT each XT2 XT4 circuit breaker can accommodate only one module configuration with external communication modules is not permitted if an internal module is present Safety As the module enables the actuator to be controlled that is connected to Ekip Touch and enables unit data to be accessed it can be connected only to networks meeting all the necessary security and unauthori...

Page 184: ...ing to mapping and rules of TCP Modbus protocol see System Interface Server HTTP Information and commands available on a web page which can be accessed by a browser by inserting the IP Address of the module as the address The page has a login window requesting the user password to be entered that is the same as the password required on the display to modify parameters Configurations on menu Activa...

Page 185: ...he case of a static IP NOTE without a DHCP server the module automatically adopts a causal IP address in the interval 169 254 xxx xxx Network Mask Subnet mask identifies the method for recognizing the subnet to which the modules belong and enables modules to be searched for within a defined set of recipients Gateway address IP address of the node to which the module is connected in the presence of...

Page 186: ...dule configuration with external communication modules is not permitted if an internal module is present Safety As the module enables the actuator to be controlled that is connected to Ekip Touch and enables unit data to be accessed it can be connected only to networks meeting all the necessary security and unauthorized access prevention requirements e g the control system network of a plant IMPOR...

Page 187: ...ch module to which it is connected NOTE in the absence of an auxiliary supply the communication between Ekip Touch and module is interrupted Menu Activating the local bus is required to start communication between the module and Ekip Touch and is available in the Settings menu page 114 If the module is detected correctly by Ekip Touch the following information is available in the About Modules men...

Page 188: ...ddress On IMPORTANT each XT2 XT4 circuit breaker can accommodate only one module configuration with external communication modules is not permitted if an internal module is present Safety As the module enables the actuator to be controlled that is connected to Ekip Touch and enables unit data to be accessed it can be connected only to networks meeting all the necessary security and unauthorized ac...

Page 189: ...es whether the module has the dynamic IP address Off or static IP address On If On all associated parameters are enabled Off Static IP address Enables the static IP to be selected 0 0 0 0 Static Network Mask Enables the subnet mask to be selected 0 0 0 0 Static Gateway address In the presence of several subnets it enables the IP address to be selected of the node to which the module is connected 0...

Page 190: ... server to be set that supplies SNTP 0 0 0 0 Time zone Defines the time zone to be used for synchronism 00 00 Daylight Saving Time Enables it to be selected whether there is daylight saving time ON or not OFF in the country to which the synchronization time refers OFF NOTE Enable IEEE 1558 and Enable SNTP client must not be enabled simultaneously Remote information From the service connector via E...

Page 191: ...n on status and measurements normally shared by Ekip Com communication modules on bus NOTE the remote open and close commands to the switch can be run only if Ekip Touch is in Remote configuration To map the module in its communication network the document System Interface is available page 128 that lists the necessary communication and command details The document also describes configuration fil...

Page 192: ...intain the Date Time in the event of absence of auxiliary alimetry NOTA refer to document 1SDH001000R0509 to replace the backup battery Connections Consult the electrical diagrams for 1SDM000068R0001 to connect the module to its communication network and for terminal references The module is supplied with a 1mt long RJ45 cable to interface with your network See the instruction sheets 1SDH002009A15...

Page 193: ...ic IP NOTE without a DHCP server the module automatically adopts a causal IP address in the interval 169 254 xxx xxx Network Mask Subnet mask identifies the method for recognizing the subnet to which the modules belong and enables modules to be searched for within a defined set of recipients Gateway address IP address of the node to which the module is connected in the presence of several subnets ...

Page 194: ...for synchronism 00 00 Daylight Saving Time Enables it to be selected whether there is daylight saving time ON or not OFF in the country to which the synchronization time refers OFF TFTP Security level Defines the file loading procedure TFTP always On port open loading still possible TFTP enable required port normally closed to start loading the Enable TFTP command must be run at the start of the p...

Page 195: ...with the SNTP server SNTP Server Synchronisation Synchronism status with SNTP server IEEE 1558 status Valid with IEEE 1588 Master ON communicates the presence Slave or PTP Master Active or absence PTP Master but Passive of a higher level master GOOSE Missing Signals whether an expected GOOSE has been received Configure Mismatch A received GOOSE does not comply with the expected structure Decode Er...

Page 196: ...68 UDP DHCP client DHCP client enabled as an alternative to Static Address On IMPORTANT each XT2 XT4 circuit breaker can accommodate only one module Configuration with external communication modules is not permitted if an internal module is present Characteristics Ekip Link has the following characteristics Integrated status contacts Open Closed and Trip Backup battery for maintaining Date Time in...

Page 197: ...tting a mask The function thus configured is subsequently referred to as logical to distinguish it from the standard that later is also referred to as hardware The protections thus selected are added to the S G D Backward and D Forward hardware ones It is possible to choose between only hardware or both hardware and logical selectivity It is possible to set the diagnostics to check for each interl...

Page 198: ...interactive data exchange network see Ekip Com Hub on page 156 IMPORTANT if Client Server the module allows data exchange as per normal Server operations Server only Enable IEEE 1558 Enable the IEEE 1588 protocol for clock signal distribution and synchronization 1 OFF Master IEEE 1588 Set the module as a master in the network segment it belongs to synchronization clock OFF IEEE 1588 delay mechanis...

Page 199: ... forwarded to the higher levels even if not active on the programmed device 0x0000 Remote information From the service connector via Ekip Connect or with system bus communication it is also possible to access additional information Information Description HW and Boot version General module information Flash CRC status and result Information on the correctness of the SW on the module Ekip Link Stat...

Page 200: ...TE refer to document 1SDH001000A0509 to replace the backup battery Security and cyber security The module uses the HTTPS protocol and can be connected to the Internet IMPORTANT it is your own responsibility to provide and constantly guarantee a secure connection between Ekip Com Hub and your or any other network depending on the case The system manager must define and maintain appropriate measures...

Page 201: ...ibution and synchronization OFF SNTP Address Server Identify the network server that provides SNTP 0 0 0 0 Password Code needed to register the module in the Cloud Remote firmware update Activation of the module s firmware update There are two parameters Enable to configure the firmware s download Automatic to automate the module s update OFF Automatic Menu information If the module is correctly d...

Page 202: ...ess of the SW on the module Publish enable configuration Enable content in the Security File Configuration file Name of the file with the information to be transmitted measurements etc Security file Name of the file with the information requested by the module to perform the transmission addresses certificates etc Certify Revocation List Name of the file containing the list of revoked certificates...

Page 203: ...EDs one for each output input The module can be set in four different configurations One in the case of a connection to a bus link network Three configurations in the event of connection via Local Bus to enable up to three modules to be connected to the same release The module can can be supplied at 110 240 VAC DC or 24 48 VDC More information on Ekip Signalling 10K is available on the website htt...

Page 204: ...nals 24Vout L and L that can be used to directly supply the Trip unit CAUTION Ekip Multimeter is sized to power only the Trip unit without additional modules If the auxiliary module voltage is used it must be connected directly to the CB terminal board without the possibility of using Ekip Supply or other modules Connections For the local bus and the auxiliary power supply Belden 3105A or equivale...

Page 205: ... Set the protections and some parameters before installation in the system With Ekip Connect software access the programming measurement and other exclusive functions Dataviewer Power Controller Load Shedding IPS IEC 61850 IMPORTANT Ekip Programming can be connected to Ekip Touch even when in use Ekip Programming only powers the display to configure and display the information of the electronic ac...

Page 206: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 206 Revisions Overhaul ECN Description B ECN000092998 Second version ...

Page 207: ...1SDH002031A1002 ECN000092998 Rev B ...

Reviews: