ABB SACE
SACE PR021/K
5.15.2.
Signals
The signals (K51/1...K51/8) for the SACE PR332/P protection release may be divided into 3 modes: Normal, Latch and
User. A description of the signals in these modes is given below.
5.15.2.1.
Normal mode (see par. 4.5.1)
The dip-switches are to be set as follows: Dip-switch no. 5 = A, Dip-switch no. 11 = OFF.
Note 1
: Following a TRIP, the status of the signals is frozen signalling the trip (K51/7) and the protection that caused
it.
Note 2: The signals bearing this marking are not frozen as indicated in Note 1.
Note 3: If dip switch no. 10 (RESET) is set to its “MAN” position, the signals may be reset as described in par. 4.2.
Note 4: If dip switch no. 10 (RESET) is set to its “AUT” position, the signals are reset automatically when the trip on
the protection unit is reset (see par. 4.2).
Note 5: If a trip is caused by a protection function not included in the set of signals (for example, a trip for “protection
G” has occurred but the K51/4 relay was set for the “LC1 load control” signal), only the K51/7 relay (the protection
release TRIP alarm) will be switched.
5.15.2.2.
Latch mode (see par. 4.5.2)
The dip-switches are to be set as follows: Dip-switch no. 5 = A, Dip-switch no. 11 = ON.
Electric
contact
Event that caused closing of the relay
Selection of dip-switches
no. 2, 3, 4
K51/1
L protection alarm or trip (overload)
---
K51/2
S protection alarm or trip (selective short-circuit)
---
K51/3
I protection trip (instantaneous short-circuit)
---
A = G protection alarm or trip (earth fault)
dip no. 2 = A
B = LC1 load control (Note 2)
dip no. 2 = B
K51/5
Communication problems on the local bus (bus KO)
---
A = L Function prealarm (overload)
dip no. 3 = A
B = LC2 load control (Note 2)
dip no. 3 = B
K51/7
Protection release TRIP alarm
---
A = Backup protection alarm (Note 2)
dip no. 4 = A
B = Hardware alarm
dip no. 4 = B
K51/8
K51/4
K51/6
Electric
contact
Event that caused closing of the relay
Selection of dip-switches
no. 2, 3, 4
K51/1
L protection alarm (overload)
---
K51/2
S protection alarm (selective short-circuit)
---
K51/3
I protection trip (instantaneous short-circuit)
---
A = G protection alarm (earth fault)
dip no. 2 = A
B = LC1 load control
dip no. 2 = B
K51/5
Communication problems on the local bus (bus KO)
---
A = L Function prealarm (overload)
dip no. 3 = A
B = LC2 load control
dip no. 3 = B
K51/7
Protection release TRIP alarm
---
A = Backup protection alarm
dip no. 4 = A
B = Hardware alarm
dip no. 4 = B
K51/8
K51/4
K51/6