42 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Ekip Touch protection trip unit | 3 - Histograms Page
3 - Histograms Page
Description
The
Histogram
page:
• This is the default
initial page
(accessed upon powering).
• It shows the histograms of the voltage and current measurements, acquired in real time by the trip unit.
Components of the page
The page appears as follow:
I
Figure 8
The following table provides a description of the various areas of the page:
Pos.
Description
A
Y-axis of the histogram, with the measurements expressed as percentage of the nominal
values set.
B
Bars that represent the measurements of phase-to-phase voltages U12 U23 U31, and of the
phase currents L1 L2 L3 and of the neutral Ne:
• In blue: no alarm.
• In yellow: voltage or current in prealarm, compared with the thresholds set (see the
chapter "9 - Touch protections" from page 61, and the chapter "10 - Measuring Pro
protections" from page 75).
• In red: voltage or current in alarm, compared with the thresholds set (see the chapter
"9 - Touch protections" from page 61, and the chapter "10 - Measuring Pro protections"
from page 75).
C
X-axis of the histogram.
NOTE:
•
The voltage histograms are shown with the Ekip Measuring accessory module.
•
The Ne current histogram is shown with circuit-breaker configured with neutral.
Continued on the next page
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...