Identification of alarms or failures | 9 - Accessories
Faults signalled on the display
The following is a list of faults that can be detected from the display and the suggestions for resolving them:
Signal
Suggestions
No Com on Local Bus
warning
Local bus enabled bus but no module present: check connection to
terminal box modules (example: Ekip Supply, Com, Contact, ecc...)
Trip coil disconnected
Check the connection of the opening solenoid
Contact Wear PreAlarm/
Alarm
Make sure that the contacts/poles are in good condition.
L1/L2/L3/Ne sensor
disconnected
Check the connection of the current sensor
Gext sensor Disconnected
Check the connection of the current sensor
Rating Plug Error
Check the connection of the Rating Plug on the front of the trip unit and
verify that the protections do not cause parameter configuration conflicts
Internal Error
Contact ABB
Invalid Date
Set the date
CB Status Error
Check the circuit-breaker status signal contacts
Rating Plug Installation
Warning
Install Rating Plug, and in the case of faults check its connection
Switchboard Actors
Communication Error
Check the configuration and connection of the Ekip Link modules
Battery Low
Change the battery on the trip unit
(1)
Voltage module Installation
warning
Install the module
Voltage Module Error
Error reading the module parameters. Contact ABB
Software Not Compatible
The Mainboard and Ekip Touch software versions are not compatible with
each other: editing of all parameters is inhibited by the display.
The protections L, I and Iinst are active and working with the parameters
set in the previous protection trip unit.
To restore compatibility please contact ABB.
(1)
Further information is available on the website http://www.abb.com/abblibrary/DownloadCenter/, where the
procedure is available
.
Consult the individual chapters describing the modules for fault finding and resolving with regard to Ekip Com
modules.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...