![ABB RMC-100 User Manual Download Page 75](http://html.mh-extra.com/html/abb/rmc-100/rmc-100_user-manual_3045290075.webp)
2105552MNAE | RMC-100 |
75
5.3
Configure low charger alarm
An alarm displays on the LCD when Low Charger Alarm is enabled and the voltage from the charger is
0.4 volts below the battery voltage. If Low Charger Alarm is disabled, the alarm does not display.
Low Charger Alarm State is read-only and displays the current state: Not in Alarm, or In Alarm.
To enable the alarm:
1.
Launch PCCU and click
View
on the menu bar. Then click
Expert
to enter Expert view.
2.
Click the station ID (the top item on the navigation tree) to display the Station Setup screen.
Scroll down to the Low Charger Alarm Enable section (
). Click the Low Charger Alarm
Value column and select
Enabled
from the drop-down list.
Figure 5-3: Low charger alarm
3.
Click
Send
.
5.4
Customize the LCD display
The maximum number of characters per row on the display is 21 (X location with a range 0 to 20).
The size of a character is 8 x 6 pixels.
The maximum number of lines on the display is 8 (Y location). Lines 3 and 6 are separator lines. Lines
7 and 8 are reserved for the annunciators. Two pairs of lines are reserved for the display items with
data, units, annunciators, and plot (optional): lines 1 (Y=0), 2 (Y=1), and 4 (Y=0), 5 (Y=1). For both
pairs, the top line has a Y location of 0. The second line has a Y location of 1. These locations indicate
position relative to the pair, not the entire height of the LCD (
Figure 5-4: LCD display items
During operation, the LCD continuously scrolls through the operating parameters.
parameters that typically display. The display is customizable.
Table 5-1: RMC display item options
Display
item
Default format
Description
Notes
DATE/TIME
MM/DD/YY
HH:MM:SS
Current Date and Time
24-hour clock
YEST DP LO
NN PERCENT
Yesterday’s Percent DP
Low Limit
Percent time below DP Low Set Point
YEST DP HI
NN PERCENT
Yesterday’s Percent DP
High Limit
Percent time above DP High Set Point
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
LINE 7
LINE 8
(Y) 0
(Y) 1
(Y) 0
(Y) 1
(X)0…………………………………………Characters…………………………………...….19 20
NAME
DATA UNITS
NAME
DATA UNITS
A2
A3
A4
A5
A6
A7
A8
A1