IMPORTANT NOTE:
If the device is configured for network communication (connected to the
corporate network or the field network), a valid IP configuration for the field network must replace
the factory IP configuration default. Local access to devices on a network is still supported after
the default configuration is replaced, but the operator laptop must have an IP configuration
compatible with the non-default addresses assigned to the devices. See section
Ethernet network communication
4.2.2.1
Enable Ethernet
Ethernet ports should be enabled if they are the preferred local connection option.
This procedure requires local connection with the RMC using either the USB or MMI ports. Establish a
, before you start this procedure. Skip this procedure
if the Ethernet ports are already enabled.
To enable Ethernet:
1.
Launch PCCU and click
Entry
. The navigation tree displays.
2.
Click
View
>
Expert
to display PCCU in Expert Mode.
3.
Click
Communications
>
Networking
.
4.
Select the State
Enable
checkbox (
5.
Click
Send
.
6.
Click
Restart
. Click
Yes
to confirm restart.
Figure 4-6: Enable Ethernet for local communication using default IP configuration
4.2.2.2
Configure the host system
If the laptop is configured to automatically obtain the IP address, do not change the TCP/IP
configuration. If the laptop has a static TCP/IP configuration, configure it for dynamic IP addressing
and private addressing (
). See
®
7 system examples.