Figure 7-11: Low calibration value reading
18.
Adjust the calibrator to apply the high value (100%) of the signal range. For example, if the
signal range of the external device is 1-5 Vdc, apply 5 Vdc.
19.
Click
100% Cal Point.
The Enter 100% Calibration Value dialog box displays (
20.
Observe the value in the Current Reading field. When it stabilizes this value should match or be
close to the signal value from the calibrator (~ 5 Vdc).
21.
Type the high range value in the field (1500 for this example) and click
OK
.
Figure 7-12: User-defined high value
The Reading column updates to reflect the signal value associated with the high value of the range