Table 345:
CMSQI Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
3I0ZeroDb
0 - 100000
m%
1
500
Zero point clamping
3I0HiHiLim
0 - 500000
A
1
3600
High High limit (physical value)
3I0HiLim
0 - 500000
A
1
3300
High limit (physical value)
3I0LowLim
0 - 500000
A
1
0
Low limit (physical value)
3I0LowLowLim
0 - 500000
A
1
0
Low Low limit (physical value)
I1ZeroDb
0 - 100000
m%
1
500
Zero point clamping
I1HiHiLim
0 - 500000
A
1
1200
High High limit (physical value)
I1HiLim
0 - 500000
A
1
1100
High limit (physical value)
I1LowLim
0 - 500000
A
1
0
Low limit (physical value)
I1LowLowLim
0 - 500000
A
1
0
Low Low limit (physical value)
I1LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
I2ZeroDb
0 - 100000
m%
1
500
Zero point clamping
I2HiHiLim
0 - 500000
A
1
1200
High High limit (physical value)
I2HiLim
0 - 500000
A
1
1100
High limit (physical value)
I2LowLim
0 - 500000
A
1
0
Low limit (physical value)
I2LowLowLim
0 - 500000
A
1
0
Low Low limit (physical value)
14.1.5.5
Monitored data
Table 346:
CMSQI Monitored data
Name
Type
Values (Range)
Unit
Description
3I0
REAL
-
A
3I0 Amplitude
3I0ANGL
REAL
-
deg
3I0 Angle
I1
REAL
-
A
I1 Amplitude
I1ANGL
REAL
-
deg
I1 Angle
I2
REAL
-
A
I2 Amplitude
I2ANGL
REAL
-
deg
I2Angle
14.1.6
Voltage sequence measurement VMSQI
14.1.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage sequence measurement
VMSQI
U1, U2, U0
SYMBOL-TT V1 EN
-
Section 14
1MRK 504 135-UEN A
Monitoring
422
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...