13.8
Integer to boolean 16 conversion with logic node
representation IB16FCVB
13.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion with
logic node representation
IB16FCVB
-
-
13.8.2
Functionality
Integer to boolean conversion with logic node representation function IB16FCVB is
used to transform an integer to 16 binary (logic) signals.
IB16FCVB function can receive remote values over IEC61850 when the operator
position input PSTO is in position remote. The block input will freeze the output at the
last value.
13.8.3
Function block
IB16FCVB
BLOCK
PSTO
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC09000399-1-en.vsd
IEC09000399 V1 EN
Figure 182:
IB16FCVB function block
13.8.4
Signals
Table 320:
IB16FCVB Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PSTO
INTEGER
1
Operator place selection
1MRK 504 135-UEN A
Section 13
Logic
401
Technical manual