12.9.4
Settings
Table 262:
I103CMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
12.10
IED commands for IEC 60870-5-103 I103IEDCMD
12.10.1
Functionality
I103IEDCMD is a command block in control direction with defined IED functions.
All outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
12.10.2
Function block
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN
Figure 159:
I103IEDCMD function block
12.10.3
Signals
Table 263:
I103IEDCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
Table 264:
I103IEDCMD Output signals
Name
Type
Description
19-LEDRS
BOOLEAN
Information number 19, reset LEDs
23-GRP1
BOOLEAN
Information number 23, activate setting group 1
24-GRP2
BOOLEAN
Information number 24, activate setting group 2
25-GRP3
BOOLEAN
Information number 25, activate setting group 3
26-GRP4
BOOLEAN
Information number 26, activate setting group 4
1MRK 504 135-UEN A
Section 12
Control
365
Technical manual