12.2.2.6
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
12.2.3
Interlocking for bus-section disconnector A1A2_DC
12.2.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for bus-section
disconnector
A1A2_DC
-
3
12.2.3.2
Functionality
The interlocking for bus-section disconnector (A1A2_DC) function is used for one
bus-section disconnector between section 1 and 2 according to figure
. A1A2_DC
function can be used for different busbars, which includes a bus-section disconnector.
WA1 (A1)
WA2 (A2)
QB
QC1
QC2
A1A2_DC
en04000492.vsd
IEC04000492 V1 EN
Figure 131:
Switchyard layout A1A2_DC
Section 12
1MRK 504 135-UEN A
Control
280
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...