execute command
SY_INPRO
SYNC_OK
t2>tSynchronizing, then
blocked-by-synchrocheck in
'cause' is set
tSynchrocheck
t1
START_SY
tSynchronizing
t2
en05000095.vsd
IEC05000095 V1 EN
Figure 125:
tSynchroCheck and tSynchronizing
Error handling
Depending on the error that occurs during the command sequence, the error signal will
be set with a value. Table
describes vendor specific cause values in addition to
these specified in IEC 61850-8-1 standard. The list of values of the “cause” are in
order of priority. The values are available over the IEC 61850. An output L_CAUSE
on the function block indicates the latest value of the error during the command.
Table 197:
Values for "cause" signal in priority order
Apparatus control
function
Description
–22
wrongCTLModel
–23
blockedForCommand
–24
blocked-for-open-command
–25
blocked-for-close-command
–30
longOperationTime
–31
switch-not-start-moving
–32
persistent-intermediate-state
–33
switch-returned-to-initial-position
–34
switch-in-bad-state
–35
not-expected-final-position
12.1.9.2
Bay control QCBAY
The functionality of the Bay control (QCBAY) function is not defined in the IEC
61850–8–1 standard, which means that the function is a vendor specific logical node.
The function sends information about the Permitted Source To Operate (PSTO) and
blocking conditions to other functions within the bay for example, switch control
functions, voltage control functions and measurement functions.
1MRK 504 135-UEN A
Section 12
Control
271
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...