Old
Calculated
S k S
1 k S
= ×
+ -
×
EQUATION1959 V1 EN
(Equation 66)
Where
S
is a new measured value to be used for the protection function
S
old
is the measured value given from the function in previous execution cycle
S
Calculated
is the new calculated value in the present execution cycle
k
TD
is settable parameter by the end user which influence the filter properties
Default value for parameter
k
is
0.00
. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay).
When
k
is set to value bigger than 0, the filtering is enabled. A typical value for
k=0.92
in case of slow operating functions.
8.8.5
Technical data
Table 123:
GOPPDOP, GUPPDUP technical data
Function
Range or value
Accuracy
Power level
(0.0–500.0)% of
SBase
± 1.0% of S
r
at S < S
r
± 1.0% of S at S > S
r
(1.0-2.0)% of
SBase
< ± 50% of set value
(2.0-10)% of
SBase
< ± 20% of set value
Characteristic angle
(-180.0–180.0) degrees
2 degrees
Timers
(0.010 - 6000.000) s
± 0.5% ± 25 ms
8.9
Negative sequence based overcurrent function
DNSPTOC
8.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative sequence based overcurrent
function
DNSPTOC
3I2>
IEC09000132 V2 EN
46
1MRK 504 135-UEN A
Section 8
Current protection
197
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...