Table 119:
GUPPDUP Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
k
0.00 - 0.99
-
0.01
0.00
Low pass filter coefficient for power
measurement, U and I
Table 120:
GUPPDUP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
-
-
Pos Seq
Mode of measurement for current and
voltage
8.8.3.5
Monitored data
Table 121:
GUPPDUP Monitored data
Name
Type
Values (Range)
Unit
Description
P
REAL
-
MW
Active Power
PPERCENT
REAL
-
%
Active power in % of
calculated power base
value
Q
REAL
-
MVAr
Reactive power
QPERCENT
REAL
-
%
Reactive power in % of
calculated power base
value
8.8.4
Operation principle
A simplified scheme showing the principle of the power protection function is shown
in figure
. The function has two stages with individual settings.
Section 8
1MRK 504 135-UEN A
Current protection
194
Technical manual