8.7.6
Monitored data
Table 108:
CCRPLD Monitored data
Name
Type
Values (Range)
Unit
Description
IMin
REAL
-
A
Lowest phase current
IMax
REAL
-
A
Highest phase current
8.7.7
Operation principle
The detection of pole discordance can be made in two different ways. If the contact
based function is used an external logic can be made by connecting the auxiliary
contacts of the circuit breaker so that a pole discordance is indicated, see figure
.
Pole discordance signal from circuit breaker
+
circuit breaker
en05000287.vsd
IEC05000287 V2 EN
Figure 84:
Pole discordance external detection logic
This binary signal is connected to a binary input of the IED. The appearance of this
signal will start a timer that will give a trip signal after the set time delay.
Pole discordance can also be detected by means of phase selective current
measurement. The sampled analog phase currents are pre-processed in a discrete
Fourier filter (DFT) block. From the fundamental frequency components of each
phase current the RMS value of each phase current is derived. The smallest and the
largest phase current are derived. If the smallest phase current is lower than the setting
CurrUnsymLevel
times the largest phase current the settable trip timer (
tTrip
) is
started. The
tTrip
timer gives a trip signal after the set delay. The TRIP signal is a pulse
150 ms long. The current based pole discordance function can be set to be active either
continuously or only directly in connection to breaker open or close command.
1MRK 504 135-UEN A
Section 8
Current protection
187
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...