8.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step residual overcurrent
protection, zero or negative sequence
direction
EF4PTOC
2
IEC11000263 V1 EN
51N/67N
8.4.2
Functionality
The four step residual overcurrent protection, zero or negative sequence direction
(EF4PTOC) has a settable inverse or definite time delay independent for step 1 and 4
separately. Step 2 and 3 are always definite time delayed.
All IEC and ANSI inverse time characteristics are available.
EF4PTOC can be set directional or non-directional independently for each of the
steps.
The directional part of the function can be set to operate on following combinations:
•
Directional current (I3PDir) versus Polarizing voltage (U3PPol)
•
Directional current (I3PDir) versus Polarizing current (I3PPol)
•
Directional current (I3PDir) versus Dual polarizing (UPol+ZPol x IPol) where
ZPol = RPol + jXPol
IDir, UPol and IPol can be independently selected to be either zero sequence or
negative sequence.
Other setting combinations are possible, but not recommended.
Second harmonic blocking level can be set for the function and can be used to block
each step individually.
1MRK 504 135-UEN A
Section 8
Current protection
155
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...