CT 300/5
in Delta
(DAC)
CT 800/5
Star
20.9 MVA
69/12.5 kV
YNd1
(YD
AC
)
CT 300/5
Star
CT 800/5
Star
20.9 MVA
69/12.5 kV
YNd1
(YD
AC
)
en06000554.vsd
IEC06000554 V1 EN-US
Figure 32:
Two differential protection solutions for star-delta connected power
transformer
For this particular power transformer the 69 kV side phase-to-earth no-load
voltages lead by 30 degrees the 12.5 kV side phase-to- earth no-load voltages. Thus
when external phase angle shift compensation is done by connecting main HV CTs
in delta, as shown in the right-hand side in figure
HV currents are rotated by 30° in clockwise direction. Thus the DAC delta CT
connection must be used for 69 kV CTs in order to put 69 kV & 12.5 kV currents
in phase.
To ensure proper application of the IED for this power transformer it is necessary
to do the following:
1. Check that HV & LV CTs are connected to 5 A CT inputs in the IED.
2. For second solution make sure that HV delta connected CTs are DAC connected.
3. For star connected CTs make sure how they are stared (that is, earthed) to/from
protected transformer.
4. Enter the following settings for all three CT input channels used for the LV side
CTs see table
1MRK 504 169-UEN A
Section 6
Differential protection
Transformer protection RET650 2.2 IEC
87
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...